Plan Review Notes For Permit 99041194 |
Permit Number |
99041194 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DESIGN OF GREASE INTERCEPTOR SHALL | | COMPLY W/CITY OF WPB UTILITIES REQS. | | CONTACT RODNEY COMPO AT (561)835-7423. | | | | SHT.CP-3.06.CONNECTION OF CONDENSATE TO | | STORM DRAIN SHALL BE BY INDIRECT | | CONNECTIONS PER SPC 804.3.,807.2, | | | | FLOOR DRAINS AT COMPACTOR SHALL BE A | | MAXIMUM OF 15' FROM THE VENT,NOT A MIN. | | OF 15'.COUNTYWIDE AMENDMENTS TO SPC SEC. | | 908.1,FOOTNOTE #1. | | | | SUBMIT DETAIL OF GAS MANIFOLD.THE | | MANIFOLD IS LOCATED NEXT TO A | | TRANSFORMER PAD THAT WILL SERVE | | EQUIPMENT THAT MAY BE CONSIDERED A | | SOURCE OF IGNITION.SUBMIT INFO ON EQUIP. | | BEING LOCATED ON PAD.COMPLY W/NFPA 54 | | SEC.1.7. | | | | SHT.CMP-3.01-VTR IS LOCATED WITHIN 10' | | OF OAI-3 .COMPLY W/SPC SEC.905.5. | | | | NOTE:EARLIER REVISIONS OF THESE PLANS | | HAVE BEEN APPROVED W/PROVISOS ON 3/21/00 | | BY T.LARGE AND THE LATER REVISIONS SHALL | | BE CORRECTED PRIOR TO APPROVAL. |
|