2001-01-08 00:00:00CAPACITY OF GREASE INTERCEPTOR SHALL BE
 DETERMINED BY CITY OF WPB UTILITIES.
 CONTACT RODNEY COMPO AT (561)835-7423
 FOR INFORMATION.
  
 DESIGN OF GREASE INTERCEPTOR SHALL
 COMPLY W/BOARD OF HEALTH REQS.
 (561)355-3022.(SEE SHT.C-MP3.04)
  
 SHT.C-P3.03-VENT FOR FLOOR DRAIN
 BY COMPACTOR SHALL RISE 6" ABOVE FLOOD
 RIM LEVEL OF FIXTURE BEFORE OFF SETTING
 PER SPC 906.2.1
  
 SUBMIT DETAIL OF GAS MANIFOLD.THE
 MANIFOLD IS LOCATED NEXT TO A
 TRANSFORMER PAD.COMPLY W/NFPA 54 SECS.
 (SOURCES OF IGNITION)1.7,(NFPA HAS BEEN
 CONTACTED FOR A CODE EXPLANATION TO
 DETERMINE IF A CODE VIOLATION EXISTS.)