Plan Review Notes For Permit 99041194 |
Permit Number |
99041194 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CAPACITY OF GREASE INTERCEPTOR SHALL BE | | DETERMINED BY CITY OF WPB UTILITIES. | | CONTACT RODNEY COMPO AT (561)835-7423 | | FOR INFORMATION. | | | | DESIGN OF GREASE INTERCEPTOR SHALL | | COMPLY W/BOARD OF HEALTH REQS. | | (561)355-3022.(SEE SHT.C-MP3.04) | | | | SHT.C-P3.03-VENT FOR FLOOR DRAIN | | BY COMPACTOR SHALL RISE 6" ABOVE FLOOD | | RIM LEVEL OF FIXTURE BEFORE OFF SETTING | | PER SPC 906.2.1 | | | | SUBMIT DETAIL OF GAS MANIFOLD.THE | | MANIFOLD IS LOCATED NEXT TO A | | TRANSFORMER PAD.COMPLY W/NFPA 54 SECS. | | (SOURCES OF IGNITION)1.7,(NFPA HAS BEEN | | CONTACTED FOR A CODE EXPLANATION TO | | DETERMINE IF A CODE VIOLATION EXISTS.) |
|