Plan Review Notes For Permit 99041039 |
Permit Number |
99041039 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SHOWER DOWNSTREAM OF WATER CLOSET SHALL | | BE VENTED PER SPC SEC.913.2. | | | | SHOW SHOWER DIMENSIONS ON PLAN.(L X W). | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | SEC.409.8.2.1. | | | | | | SPC SEC.104.2.1. | | | | SIZE OF WASTE STACK SHALL COMPLY W/SPC | | SEC.909.3.1. | | | | IF SINK AND D/W ARE NEW SHOW ON SAN. | | RISER DIAGRAM.SPC SEC 104.2.1. | | | | INDICATE TYPE OF PIPING TO BE USED FOR | | GAS INSTALLATION. STD.GAS CODE SEC.306. | | | | SUBMIT CALCULATIONS FOR COMBUSTION AIR. | | COMPLY W/STD.GAS CODE SEC.402.4 | | | | SUBMIT EXIST.BTU LOAD ON SYSTEM FROM | | GUEST HOUSE TO ENSURE PROPER SIZING OF | | GAS SYSTEM.STD.GAS CODE SEC.305.1.1.& | | SHOW DELIVERY PRESSURE OF GAS. |
|