2001-01-08 00:00:00SHOWER DOWNSTREAM OF WATER CLOSET SHALL
 BE VENTED PER SPC SEC.913.2.
  
 SHOW SHOWER DIMENSIONS ON PLAN.(L X W).
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.409.8.2.1.
  
  
 SPC SEC.104.2.1.
  
 SIZE OF WASTE STACK SHALL COMPLY W/SPC
 SEC.909.3.1.
  
 IF SINK AND D/W ARE NEW SHOW ON SAN.
 RISER DIAGRAM.SPC SEC 104.2.1.
  
 INDICATE TYPE OF PIPING TO BE USED FOR
 GAS INSTALLATION. STD.GAS CODE SEC.306.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/STD.GAS CODE SEC.402.4
  
 SUBMIT EXIST.BTU LOAD ON SYSTEM FROM
 GUEST HOUSE TO ENSURE PROPER SIZING OF
 GAS SYSTEM.STD.GAS CODE SEC.305.1.1.&
 SHOW DELIVERY PRESSURE OF GAS.