Plan Review Notes For Permit 99041007 |
Permit Number |
99041007 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO***************** | | | | NEED FAULT CURRENT CALCULATIONS FOR | | AIC RATING.ART.215-5 | | NOTE:GROUNDING ELECTRODE COND. TO | | GROUND ROD ALSO. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS. | | NOTE:MISSING COND. UNIT AND DISC. | | | | NEED ABOVE INFORMATION BEFORE FINAL | | IS CALLED IN. |
|