Plan Review Notes
Plan Review Notes For Permit 99040822
Permit Number 99040822
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO******************
  
 NEED FAULT CURRENT CALCULATIONS FOR
 AIC RATING.ART.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:REQ`MENTS FOR KITCHEN RECEPTS.
 ART.210-8-A-6
 NOTE:GROUNDING ELECTRODE SYSTEM TO
 GRND.ROD,CWP,AND BLDG.STEEL.
  
 NEED THE ABOVE INFORMATION BEFORE
 FINAL INSPECTION IS CALLED IN.