Plan Review Notes
Plan Review Notes For Permit 99040821
Permit Number 99040821
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO****************
  
 NEED FAULT CURRENT CALCULATIONS FOR AIC
 RATING.215-5
 NOTE:SERVICE GROUNDING ELECTRODE SYSTEM
 TO GROUND ROD AND BLDG. STEEL.
 NOTE:REQ`MENTS FOR KITCHEN RECEPTS.
 ART.210-8-A-6
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved