Plan Review Notes
Plan Review Notes For Permit 99040563
Permit Number 99040563
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO*****************
  
 NOTE:NEED ELEC.RISER DIAGRAM FOR UNIT
 'A'.PANEL,CONDUITS,WIRE.GROUNDING
 SYSTEM.215-5
 NOTE:SERVICES TO COLD WATER PIPE ALSO.
 NOTE:RECEPT.REQ`D FOR A/C COND.UNIT.
 210-63
  
 NEED ABOVE INFORMATION BEFORE ROUGH
 INSPECTION IS CALLED.!!!!!!