2001-01-08 00:00:00 | ****************PROVISO***************** | | | | NOTE:NEED FAULT CURRENT CALCULATIONS | | FOR AIC RATING.215-5 | | NOTE:GROUNDING ELECTRODE SYSTEM IS TO | | HAVE GRND.ROD,CWP,AND BLDG.STEEL. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS. | | NOTE:ART.210-8-A-6 RECEPTS. SERVING | | KITCHEN COUNTER TO BE GFI/PROTECTED. | | NOTE:210-52A REC.REQ`D 2'6'12'RULE. | | NOTE:KITCHEN PENINSULAR TO MEET ART`S | | 210-52-C-3/210-52-C-5. |
|