2001-01-08 00:00:00****************PROVISO*****************
  
 NOTE:NEED FAULT CURRENT CALCULATIONS
 FOR AIC RATING.215-5
 NOTE:GROUNDING ELECTRODE SYSTEM IS TO
 HAVE GRND.ROD,CWP,AND BLDG.STEEL.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:ART.210-8-A-6 RECEPTS. SERVING
 KITCHEN COUNTER TO BE GFI/PROTECTED.
 NOTE:210-52A REC.REQ`D 2'6'12'RULE.
 NOTE:KITCHEN PENINSULAR TO MEET ART`S
 210-52-C-3/210-52-C-5.