Plan Review Notes
Plan Review Notes For Permit 99040478
Permit Number 99040478
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00KITCHEN LTS/RECEPTS.NEED TO BE SEPARATED
 BATH LTS/RECEPTS.NEED TO BE SEPARATED
 ALSO!
 RECEPTS.IN KIT.EXT.IF THERES WORK DONE
 IN THAT AREA THEN THEY NEED TO BE ON
 20A CIRCUT.
 NEED COMPLETE RISER DIAGRAM TO SHOW
 PANEL/CONDUITS/WIRE SIZE/AND NEED NEW
 LOAD CALCULATION.215-5
 BATHS REFER TO 210-52D
  
 ALL INFORMATION IS REQ`D BEFORE ROUGH
 INSPECTION IS CALLED!!!!!!!!!! D.V.P.