2001-01-08 00:00:00EXISTING DUCT TO BE INSPECTED FOR CLEAN-
 LINESS AND IF DEEMED NECESSARY CLEANED
 AND SANITIZED BY LICENSED MECHANICAL
 CONTRACTOR
 2)FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 PER 1994 SMC 406.1
 3)NOTIFICATION REQUIRED PER NFPA 90A 4-4
 .4.3 BY HORN AND STROBE