Plan Review Notes For Permit 99031479 |
Permit Number |
99031479 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CLEARLY SHOW ALL SHOWER DIMENSIONS ON | | PLAN.(L X W).MIN.1024 SQ.IN.REQ'D & MIN. | | 30" WIDE.PER SPC SEC.408.8.1,409.8.2.1 | | OF COUNTYWIDE AMEND. | | | | SHOW LOCATION OF WASHING MACHINE OUTLET | | SPC 104.2.1. | | | | SHOW LOCATION OF WATER HEATERS.SPC | | 401.2.1 | | | | SUBMIT SANITARY RISER DIAGRAM THAT | | COMPLIES W/STD.PLBG.CODE. | | | | SHOW FIXTURE CLEARANCES OF W.C'S ON PLAN | | PER SPC SEC.403.4. | | | | VENTING OF WATER CLOSETS SHALL COMPLY | | W/COUNTYWIDE AMEND.TO PLBG.CODE SEC. | | 911.1.3. | | | | KIT.SINK NOT PROPERLY VENTED.SPC 901.2. | | | | SHOW ALL FIXTURES ON SAN.RISER.SPC 104.2 | | | | DRY VENTS NOT PERMITTED. |
|