Plan Review Notes
Plan Review Notes For Permit 99031479
Permit Number 99031479
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CLEARLY SHOW ALL SHOWER DIMENSIONS ON
 PLAN.(L X W).MIN.1024 SQ.IN.REQ'D & MIN.
 30" WIDE.PER SPC SEC.408.8.1,409.8.2.1
 OF COUNTYWIDE AMEND.
  
 SHOW LOCATION OF WASHING MACHINE OUTLET
 SPC 104.2.1.
  
 SHOW LOCATION OF WATER HEATERS.SPC
 401.2.1
  
 SUBMIT SANITARY RISER DIAGRAM THAT
 COMPLIES W/STD.PLBG.CODE.
  
 SHOW FIXTURE CLEARANCES OF W.C'S ON PLAN
 PER SPC SEC.403.4.
  
 VENTING OF WATER CLOSETS SHALL COMPLY
 W/COUNTYWIDE AMEND.TO PLBG.CODE SEC.
 911.1.3.
  
 KIT.SINK NOT PROPERLY VENTED.SPC 901.2.
  
 SHOW ALL FIXTURES ON SAN.RISER.SPC 104.2
  
 DRY VENTS NOT PERMITTED.