Plan Review Notes
Plan Review Notes For Permit 99030844
Permit Number 99030844
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1994 SMC 406.1
 2) NOTIFICATION REQUIRED PER 1996 NFPA
 90A 4-4.4.2 OR 4-4.4.3 OF FAN SHUT DOWN