Plan Review Notes
Plan Review Notes For Permit 99030676
Permit Number 99030676
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********UNSAT***********************
  
 1)NOTE: NEED LOAD CALCULATIONS AS PER
 220-3-D-1
 2)NOTE: NEED TO SHOW SIZE OF EXISTING
 SERVICE TO INCLUDE SERVICE WIRE SIZE.
 3)NOTE: NEED TO SHOW NEW PANEL SCHEDULE
 FOR ADDITION OF NEW CIRCUTS TO EXISTING
 PANEL. DINING AREA REQ`S 20 AMP BRANCH
 CIRCUTS AS PER CODE.
 4)NOTE: ALSO AS PER 210-52D BATH REC IS
 TO ON IT`S OWN 20 AMP BRANCH CIRCUT.
 5)NOTE: PLEASE SHOW EXISTING LOCATION
 OF REC AT REAR OF RESIDENCE AS REQ`D BY
 210-52 E IF NO REC EXIST THEN ONE NEEDS
 TO BE ADDED TO REAR OF ADDITION.
 6)NOTE: NEED TO HAVE SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL NEW BEDROOMS
 AS REQ`D BY NFPA-72 2-2.1.1.1 1993/1996
 EDDITION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS OR I CAN BE OF ANY ASST.
 PLEASE CONTACT ME AT 659-8096 EXT8372