2001-01-08 00:00:00**************DENIED********************
  
 NEED RISER DIAGRAM TO SHOW COMPLETE
 SERVICE!
 IF TWO SEPARATE EXIST THEN NOW THEY NEED
 TO BE GROUPED AS PER ART. 230-72
 NEED NEW LOAD CALCS. DO TO ADDITIONAL
 ELECTRICAL WORK.
 NOTE MEANS OF EGRESS TO PORCH REQ`S
 SWITCH FOR LIGHTING.210-70
  
 **************PROVISO 6/22/99***********
 NEED TO SUBMIT AIC RATING FOR EQUIP.
 AND PANEL SCHED. ART.215-5
 NOTE:OUTSIDE LIGHT REQ`D 210-70
 NOTE:NOT TO USE DISC.AS RACEWAY.