Plan Review Notes
Plan Review Notes For Permit 99021077
Permit Number 99021077
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
 (1) SHT 3.1 WATER HEATER ABOVE CEILING,
 SHOWER TO BE READLY ACCESSIBLE SEC 501.7
 SHOW A DETAILOF THE STATIONARY LADDER
 FOR THE COMPLIANCE OF THIS SECTION.
 (2) SHT 4.1 SHOW LOCATION OF BACK FLOW
 PREVENTER ON WATER SERVICE.
 (3) SHT LS-2 PROVIDE IRRIGATION PLANS AS
 PER NOTE FOR IRRIGATION.
 END OF COMMENTS