Plan Review Notes For Permit 99020714 |
Permit Number |
99020714 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CHECKLIST - MODEL IV: | | 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS | | DRAWINGS PRIOR TO SUBMITTAL. | | 2-ENGINEERED TRUSSES: | | *CHECK/REVISE MEAN ROOF HEIGHT. | | *CLARIFY NOTE #1 ON ENGINEERED ROOF | | TRUSSES. EG: IF PORCHES EXIST, THEY | | ARE NOT EXPOSED TO WIND. WHY? | | WHAT DOES DOL STANDS FOR?DEFLECTION? | | *REVISE DESIGN CRITERIA DATA ON TRUSS | | LAYOUT. IT DOESN'T MATCH DESIGN | | CRITERIA ON ENGINEERED TRUSSES. | | *REVISE DIMENSIONS OF BUILDINGS SHOWN | | ON ENGINEERED TRUSSES. | | *WHY NOT ALL ENGINEERED TRUSSES SHOW | | THE DESIGN CRITERIA USED TO DETERMINE | | ALL THE LOADS. | | 3-CHECK/REVISE ALL HURRICANE ANCHORS | | SPECIFIED. WILL THEY RESIST THE | | HORIZONTAL LOADS CALCULATED BY THE | | ENGINEERED TRUSSES. | | 4-PROVIDE A COMPLETE DETAIL FOR ALUMINUM | | CEILINGS AT PORCH. |
|