Plan Review Notes
Plan Review Notes For Permit 99020713
Permit Number 99020713
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CHECKLIST - MODEL V:
 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE.
 2-ENGINEERED TRUSSES: REVISE MEAN ROOF
 HEIGHT.THIS IS A TWO STORY BUILDING.
 REMAINDER THERE IS ONLY ONE MEAN ROOF
 HEIGHT FOR ENTIRE BUILDING.
 3-PROVIDE COMPLETE DETAIL AND SPECS FOR
 LEDGER TO RECEIVE ROOF TRUSSES AT
 FRONT PORCH. SEC 104.2.2 CITY AMENDMEN
 4-PROVIDE COMPLETE SECTIONS/DETAILS FOR
 TWO STORY WALL SECTIONS. SPECIFY ALL
 CONNECTORS. SHEARWALLS. TRANSITION
 FROM FIRST FLOOR TO SECOND FLOOR. NOTE
 THAT THERE ARE TWO CONDITIONS: ONE
 WHEN EXTERIOR WALL IS PERPENDICULAR TO
 2ND FLOOR FRAMING AND ONE WHEN IT'S
 PARALLEL.
 5-CHECK/REVISE IF ALL HURRICANE ANCHORS
 SPECIFIED WILL BE ABLE TO RESIST THE
 HORIZONTAL LOADS SPECIFIED BY THE
 ENGINEERED TRUSSES.
 6-CLARIFY NOTE #1 ON ENGINEERED TRUSSES.
 FOR EXAMPLE, TRUSS JO5 AT FRONT PORCH
 SAYS IF PORCHES EXIST, THERE ARE NOT
 EXPOSED TO WIND. WHY?
 WHAT DOES DOL STANDS FOR?
 REVISE DESIGN CRITERIA DATA ON TRUSS
 LAYOUT. IT DOESN'T MATCH DESIGN
 CRITERIA SHOWN ON ENGINEERED TRUSSES.
 7-PROVIDE A COMPLETE DETAIL FOR ALUMINUM
 CEILINGS AT PORCH.