Plan Review Notes
Plan Review Notes For Permit 98120351
Permit Number 98120351
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW UNSAT, 94 STD PLBG
 CODE CONTACT PAUL SHMITZ 561-659-8096
 X 8233.
 (1) SHT. M-1 EX. GREASE TRAP NOT APPR.
 MINIMUM SIZE 750 GAL. REQUIRED.
 (2) ALL INDIRECT WASTE TO FLOOR SINKS.
 (3) SEPERATE GREASE WASTE FROM SANITARY
 WASTE, (ICE CREAM, FOOD DISPENSING.)
 (4) GAS WATER HEATER: COMBUSTION AIR
 AS PER STD GAS CODE 94 SEC.402.4.
 END OF COMMENTS
 PROVISO: 02-03-99 SEE SHT. M-1 & M-2