Plan Review Notes
Plan Review Notes For Permit 98120351
Permit Number 98120351
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00A/C SCHEDULE DOES NOT REFLECT SAME AS
 DRAWING I.E. 1&4 NOT 1&2
 NO EER SHOWN FOR AHU #4
 CFM VALUE FOR AHU #1 DOES NOT MATCH
 MODEL NUMBER APPERANT TONNAGE
 AHU #2 REQUIRES FAN SHUT DOWN BY DUCT
 SMOKE DETECTOR
 SEPARATE PERMIT REQUIRED FOR HOOD AND
 SUPPRESSION SYSTEM FOR HOOD INCL.PLANS