2001-01-08 00:00:00SANITARY AND WATER RISER SHALL CORRELATE
 W/FLOOR PLAN.SPC 104.2.1.
  
 FIXTURES DISCHARGING DOWNSTREAM OF WATER
 CLOSETS SHALL BE VENTED PER SPC SEC.
 913.2.
  
 WASHING MACHINES SHALL BE TRAPPED PER
 SPC 1001.2.
  
 MIN.SIZE OF U/G DRAINAGE SHALL BE 2" PER
 SPC SEC.714.4.
  
 MAIN VENT REQUIRED IN DRAINAGE SYSTEM
 PER SPC SEC.904.3.
  
 INDICATE SLOPE OF PIPE FOR SANITARY
 SYSTEM ON PLANS.COMPLY W/SPC SEC.714.1,
 714.2.
  
 HEAT TRAPS ARE REQ'D. ON THE WATER
 HEATER PER FLA.ENERGY CODE SEC.
 612.1ABC.2.2.
  
 SUBMIT SYSTEM LISTING NUMBER FOR FIRE
 RESISTANCE INTEGRITY OF PIPE PENETRATION
 THROUGH RATED WALLS.COMPLY W/SBC.SEC.
 104.2.4.
  
 SANITARY ISOMETRIC SHOWS DRY VENTS.
 CLARIFY.SPC.104.2.1.