Plan Review Notes For Permit 23070859 |
Permit Number |
23070859 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-24 14:12:38 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, | | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE ARE INDICATIONS OF VINYL FLOORING BUT NO | | SPECIFICATIONS SHEETS THAT INDICATE MEETING THE | | REQUIREMENTS PER NFPA' | | | | PER NFPA 101, CHAPTER 10 SECTION 10.2.7 | | | | 10.2.7* INTERIOR FLOOR FINISH TESTING AND | | CLASSIFICATION. | | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR | | FINISHES SHALL | | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR | | IGNITION | | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING | | MATERIALS. | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN | | THE CLASSES SPECIFIED | | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE | | CRITICAL RADIANT FLUX | | REQUIREMENTS. | | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I | | INTERIOR FLOOR FINISH | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | 0.45 W/CM2, AS DETERMINED | | BY THE TEST DESCRIBED IN 10.2.7.3. | | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II | | INTERIOR FLOOR FINISH | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | 0.22 W/CM2, BUT LESS | | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN | | 10.2.7.3. | | | | PLEASE REVIEW AND PROVIDE SPEC SHEETS. | | | | | | | | CAITLIN L FRANCIS | | FIRE INVESTIGATOR | | 561-804-4728 | | [email protected] | | |
|