Plan Review Notes For Permit 23070283 |
Permit Number |
23070283 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-14 14:04:11 | FIRE PROVISO: | | | | THERE IS AN INDICATION OF FLOOR TILE TBD. | | | | TILE FLOORING CAN HAVE DIFFERENT MEANINGS AND CAN BE | | MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE TESTED | | AND MEETING LISTED AND NFPA STANDARDS. | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE | | FLOORING TYPE, PRODUCT NAME AND, IF APPLICABLE, THE | | PRODUCT SPEC SHEETS INDICATING THE FIRE BEHAVIOR | | RATING. | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | WOULD NOT BE REQUIRED, BUT NEEDS TO BE INDICATED ON THE | | PLAN. | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | FLOORING, WOOD/VINYL LAMINATES, ETC. | | | | | | PROVIDE A SUBMITTAL OF INFORMATION WITH THE FLOOR TILE | | TYPE IS OTHER THAN PORCELAIN/CERAMIC TILE, NATURAL | | STONE TILE, OR CONCRETE TILES. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|