Plan Review Notes For Permit 23070089 |
Permit Number |
23070089 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-13 13:07:14 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 23070089 | | 7/13/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SUBMITTED SPECS FOR THE LIBERTY PRO SERIES 370 | | SEWERAGE PUMP WITH 2-INCH INDICATES RESIDENTIAL USE. | | THERE IS NOT ENOUGH INFORMATION PROVIDED TO DETERMINE | | IF THE PUMP CAN HANDLE THE GPM FLOW FROM THE | | RESTAURANT. PLEASE CLARIFY HOW THE PUMP WAS SIZED AND | | SELECTED AND NOTE THAT A COMMERCIAL GRADE MAY BE | | REQUIRED FOR PERMITTING- SECS. 712.3.1 FBC P. | | | | 2) PROVIDE A PIPING DIAGRAM FOR THE LIFT STATION- | | 712.1- 712.3.2 FBC P. | | | | 3) PROVIDE AN ELECTRICAL PLAN OR DIAGRAM- SEC. 107.2.1 | | WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|