2023-07-10 13:04:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A NEW DDCV BUT NO TO
 CONFIRM THE PROPOSED MEET CITY STANDARDS.
  
 NFPA
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED DDCV.
  
  
 2) THERE ARE MANY DDCV'S SHOWN ON THE SITE PLAN.
  
 PLEASE HIGHLIGHT OR CLOUD THE CORRECT #'D DDCV FOR EASY
 IDENTIFICATION OF THIS INSTALL AND ALL FUTURE INSTALLS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE
 SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND
 INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF
 THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO
 THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT
 INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS
 NOT INCLUDED. [5000:1.7.6.3.3.3]
  
 PLEASE HIGHLIGHT THE PROPOSED DDCV UNDER THIS PERMIT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  