Plan Review Notes For Permit 23070002 |
Permit Number |
23070002 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-07-18 08:19:17 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 23070002 | | 7/18/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST | | REVIEW LISTED BELOW STILL EXISTS- PLEASE COMPLY. | | | | 1) THE PERMIT APPLICATION INDICATES BACKFLOW #3 RPPA | | FOR 6" WATER SERVICE, HOWEVER THE BF TABLE ON SHEET EX | | 1 SITE PLAN INDICATES BACKFLOW #3 TO BE A 6" DDCA FOR | | FIRE LINE. PLEASE CORRECT ONE OR THE OTHER- SEC. | | 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|