Date |
Text |
2023-07-06 14:17:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF NEW FLOORING ON ONE OF THE |
| FLOOR PLANS HOWEVER, THERE IS NO SPEC SHEET NOR A |
| PRODUCT NAME FOR THE ACTUAL PROPOSED FLOORING. |
| |
| FLOORING CAN HAVE DIFFERENT TYPES AND CAN BE |
| MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE TESTED |
| AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| THE CLASSES SPECIFIED |
| IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| CRITICAL RADIANT FLUX |
| REQUIREMENTS. |
| 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| 0.45 W/CM2, AS DETERMINED |
| BY THE TEST DESCRIBED IN 10.2.7.3. |
| 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| 0.22 W/CM2, BUT LESS |
| THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| 10.2.7.3. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| TYPE, PRODUCT NAME AND, IF APPLICABLE, THE PRODUCT SPEC |
| SHEETS INDICATING THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED, BUT NEEDS TO BE INDICATED ON THE |
| PLAN. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| 2) THERE ARE INDICATION OR WLL & CEILIGN WORK |
| THROUGHOUT THE UNIT. |
| |
| DO NOT PAINT OVER FIRE ALARM DEVICES/EQUIPMENT. |
| |
| THE FA SYSTEM SHALL BE MAINTAINED THROUGHOUT DEMO AND |
| CONSTRUCTION. |
| |
| ANY WORK/DAMAGE ON THE FA SYSTEM SHALL BE |
| CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP |
| DRAWING BY FA CONTRACTORS. |
| |
| PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |