Plan Review Notes For Permit 23061476 |
Permit Number |
23061476 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-07-13 13:35:53 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY | | CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA | | REGISTERED PROFESSIONAL ENGINEER/ARCHITECT; TO CORRECT | | DESIGN PRESSURES & NAILING PATTERNS. EXAMPLE: THE | | CORRECT DESIGN PRESSURE FOR EXPOSURE D; ZONE 3; GABLE | | ROOF 0 TO 7 DEGREES; MEAN ROOF HEIGHT UP TO 15 FT AS | | PER TABLE R301.2(2) & TABLE R301.2(3) OF THE 2020 FBC R | | IS -131.42. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|