Plan Review Notes
Plan Review Notes For Permit 23061431
Permit Number 23061431
Review Stop P
Sequence Number 1
Notes
Date Text
2023-07-24 14:20:261ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23061431
 7/24/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FB
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C-201: PLEASE SHOW THE LOCATION OF THE
 EXISTING BACKFLOW PREVENTER FOR THE POTABLE WATER
 SERVICE- SEC. 608.1 FBC P, & SEC. C WPB UTILITIES CROSS
 CONNECTION MANUAL. PLEASE NOTE THAT REPLACEMENT OR
 RELOCATION OF THE DEVICE SHALL BE UNDER A SEPARATE
 PERMIT- SECS. 105.1 & 107.2.1 WPB.
  
 2) A1.0 & A1.3: PLEASE SHOW THE ACCESSIBLE ROUTE/PATH
 OF TRAVEL FROM BUILDING #3 TO BUILDING #1 RESTROOMS
 FROM THE MOST REMOTE POINT OF BUILDING #3 AND INCLUDE
 THE LENGTH OF THE ROUTE- SECS. 403.3.1 & 403.3.3 FBC P.
  
 3) A3.0 & A6.0: THE DRINKING FOUNTAINS AND GROUP WASH
 SINK APPEAR TO HAVE LEADING EDGES BETWEEN 27-INCHES AND
 80-INCHES THAT ARE PROTRUDING INTO THE CIRCULATION
 PATH- SEC. 307.2 FBC ACC. THE FIXTURES SHALL EITHER BE
 INSTALLED IN A NICHE, OR BETWEEN BARRIERS ON OPPOSING
 SIDES, OR EQUIPPED WITH SKIRTING FOR CANE SWEEP
 DETECTION.
  
 4) A3.0 & A6.0: ACCESSIBLE PLUMBING FIXTURE AND
 ACCESSORY INSTALLATION COMPLIANCES CANNOT BE APPROVED
 WITHOUT MOUNTING HEIGHT AND CLEARANCE MEASUREMENTS
 ATTACHED TO THE DETAILS. PLEASE SHOW-
  
 A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
  
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 C) HEIGHTS OF THE LAVATORY SINKS AND GROUP WASH SINK
 RIMS OR COUNTER SURFACES FROM THE FINISHED FLOORS- SEC.
 606.3.
  
 D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3.
  
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
  
 F) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
  
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 H) HEIGHT OF THE URINAL RIM- SEC. 605.2.
  
 I) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2.
  
 J) SPOUT HEIGHTS OF THE HI AND LO DRINKING FOUNTAINS-
 SEC. 602.4 & 602.7.
  
 K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE SHOWERS- SEC. 608.3.1.
  
 L) SHOWER SEAT DIMENSIONS AND MOUNTING HEIGHTS AND
 CLEARANCES- SECS. 610.2 & 610.3.2.
  
 M) CLEAR FLOOR SPACE APPROACHES TO THE KITCHEN AND
 CONFERENCE SINKS, AND THE HEIGHTS OF THE SINK RIMS OR
 COUNTER SURFACES- SECS. 606.2 & 606.3.
  
 5) A1.1A, P301, P601: A SOLIDS INTERCEPTOR AND A GREASE
 INTERCEPTOR SHALL BE INSTALLED TO RECEIVE THE DRAINAGE
 FROM THE SINK, DISHWASHERS, AND THE FOOD DISPOSER-
 SECS. 1003.3,1 & 1003.3.2 FBC P. A SEPARATE PERMIT AND
 PLANS ARE REQUIRED FOR INSTALLATION OF THE INTERCEPTORS
 HOWEVER THE FOLLOWING INFORMATION SHALL ALSO BE
 PROVIDED ON THE MAIN PLAN. REFER TO SEC. 1003.3.5 AND
 PROVIDE-
  
 A) MAKE AND MODEL NUMBERS OF THE INTERCEPTORS AND
 GALLON CAPACITIES.
  
 B) SIZING CALCULATIONS.
  
 C) PIPING DIAGRAM INCLUDING LOCATIONS AND SIZES OF
 INLETS, OUTLETS, CLEANOUTS, AND VENT PIPING.
  
 6) P401 & P602: THE 1/2-INCH HOT WATER FIXTURE SUPPLY
 PIPES TO THE PUBLIC LAVATORIES ARE EXCEEDING THEIR
 MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER
 SOURCE WHICH IS THE RECIRCULATION LINE- SEC. C404.5.1
 FBC ENERGY.
  
 7) P401, P602, & P801: PROVIDE THE MAKE AND MODEL OF
 THE EMERGENCY EYE WASH STATION; INDICATE IT CONFORMS TO
 ISEA Z358.1, AND IS EQUIPPED WITH AN ASSE 1071 MIXING
 VALVE FOR TEPID WATER DELIVERY BETWEEN 60-100 DEGREES
 F.- SECS. 411.1 & 411.3 FBC P.
  
 8) A1.5 & P302 ROOF DRAINAGE:
  
 A) PROVIDE THE RAIN FALL RATE- SEC. 1106.1 FBC P.
  
 B) PROVIDE ROOF AREA AND GPM FLOW CALCULATIONS- 1106.2.
  
 C) PROVIDE THE GUTTER AND DOWNSPOUT SIZES- 1106.3 &
 1106.6.
  
 D) SHOW DOWNSPOUT LOCATIONS- 1106.3.
  
 E) SHOW THE DRAINAGE DISPOSAL LOCATIONS- SEC. 1101.2.
  
 9) CONCERNING THE BACKFLOW PREVENTER AND GREASE
 INTERCEPTOR- PERMIT APPLICATIONS SHALL BE SUBMITTED
 PRIOR TO MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  