Plan Review Notes For Permit 23061410 |
Permit Number |
23061410 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-12 11:55:17 | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | FAULT CURRENT IS LISTED AT 65K. PLEASE SHOW CALCULATION | | PER 110.9, AND 110.10 AND LABELED PER 110.24. | | | | PLEASE SUBMIT THE SPECIFICATION FOR THE CHARGERS 110.3 | | | | PLEASE SUBMIT A COST BREAKDOWN FOR THE INSTALLATION | | SHOWING LABOR AND ALL MATERIALS TO COMPLETE THIS KOB. | | 165K FBC 109.2.1 |
|