2023-07-06 15:01:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE SPEC SHEET STATES: |
| |
| INSTALLATION GUIDELINES |
| |
| 1) EXHAUST IS AIMED AWAY FROM OR PARALLEL TO THE |
| STRUCTURE. |
| |
| 2) EXHAUST IS NOT DIRECTED AT PLAY AREAS, PATIOS OR |
| OTHER AREAS WHERE PEOPLE CONGREGATE. |
| |
| 3) THE NEAREST WINDOW, VENT, DOOR OR SIMILAR STRUCTURE |
| OPENING IS AT LEAST 5 FEET FROM THE EXHAUST END OF THE |
| GENERATOR. |
| |
| 4) GENERATOR SET MUST BE INSTALLED A MINIMUM OF 18 |
| INCHES FROM STRUCTURE PER NFPA 37, HOWEVER, ACTUAL |
| DISTANCE MAY DIFFER BASED ON STATE AND LOCAL CODES. |
| |
| 5) WINDOWS & DOORS ON ADJACENT WALLS ARE CLOSED. |
| |
| 6) FURNACE AND OTHER SIMILAR INTAKES ARE AT LEAST 10 |
| FEET FROM EXHAUST END OF GENERATOR. |
| |
| |
| THE FLOOR PLAN DOES NOT INDICATE DETAILS IN COMPLIANCE |
| WITH THE INSTALLATION GUIDELINES. |
| |
| PLEASE REVIEW AND PROVIDE THE APPLICABLE SPECIFIC |
| DETAILS/DIMENSIONS. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF A NG LINE HOWEVER, THERE |
| ARE NO DETAILS PER NFPA 54, INCLUDING SERVICE LINE |
| LEENGTH, DEPTH OF COVERAGE, NEW GAS METER DIMENSION |
| FROM AN ELECTICAL SPARK SOURCE, ETC. |
| |
| PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE ALL |
| APPLICABLE AND REQUIRED DIMENSIONS. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |