Plan Review Notes For Permit 23061309 |
Permit Number |
23061309 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-12 15:39:03 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.2.1 SPECIFY THE SPECIFIC MOUNT TYPE, | | FASTENER TYPE AND FASTENER SPACING FOR THE TOP AND | | BOTTOM TRACKS AT EACH OF THE OPENINGS (1,2,3 & 4) THAT | | WILL BE USED TO INSTALL THE ACCORDION SHUTTERS. YOU | | HAVE CIRCLED MULTIPLE ITEMS ON THE PRODUCT APPROVAL, | | BUT YOU DIDN'T SPECIFY WHICH OPENING THEY WILL BE USED | | FOR. SUBMIT AN INSTALLATION SCHEDULE THAT LISTS EACH | | OPENING AND PROVIDE THE REQUIRED INSTALLATION | | INFORMATION FOR EACH. | | | | 2) SPECIFY THE SUBSTRATE (CONCRETE, WOOD, ETC.) THAT | | YOU WILL BE ANCHORING TO AT THE TOP AND BOTTOM OF EACH | | OPENING IN THE SCHEDULE. FBC 107.2.1 | | | | 3) THE ACTUAL MEAN ROOF HEIGHT OF THE BUILDING IS USED | | TO DETERMINE THE DESIGN PRESSURES FOR ALL OF THE | | OPENINGS. THE HEIGHT OF THE OPENING ITSELF IS NOT USED. | | THE TABLE OFF DESIGN PRESSURES FOR COMPONENTS AND | | CLADDING HAS A COLUMN FOR MEAN ROOF HEIGHT NOT OPENING | | HEIGHT. FBC 1609 | | |
|