2023-07-24 17:45:03 | BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23061300 |
| 600 S DIXIE HWY # 251 |
| |
| NOTE: |
| LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| THE FLORIDA BUILDING CODE. |
| |
| 1- PERMIT APPLICATION CALLS FOR INSTALLATION OF VINYL |
| FLOORING PLANKS. COPIES OF THE UNDERLAYMENT TEST |
| SUBMITTED ARE FOR LAMINATED FLOORING. NEED TO PROVIDE |
| TEST COPIES FOR VINYL PLANKS. SEE COMMENTS BELOW: |
| |
| FLOORING SOUND INSULATION MATERIAL: |
| (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 AND 720.2 OF FBC |
| 7TH EDITION (2020). |
| |
| (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| |
| (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| FLOOR FINISH. |
| NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH |
| OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT |
| SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |