Plan Review Notes For Permit 23061272 |
Permit Number |
23061272 |
|
Review Stop |
SIGNATURE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-27 13:19:19 | CONCRETE PAD ENGINEER???S DIGITAL SIGNATURE: | | 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | REQUIREMENTS OF FBPE: | | A)THE TEXT BOX LANGUAGE MUST BE IDENTICAL TO THE | | SAMPLES PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-A | | ND-SEALING-ENGINEERING-DOCUMENTS/??? AND REVISE AS | | REQUIRED TO MATCH. | | | | B)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | DIGITAL SIGNATURE ITSELF. | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | MENTS/ AND REVISE AS REQUIRED. | | | | NOTE: | | THESE COMMENTS WERE VERIFIED WITH THE FBPE | | INVESTIGATOR. THE TEXT BOX REQUIREMENTS APPLY | | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | |
|