2023-06-27 15:19:16 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 23061126 |
| 6/27/23 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS |
| AND NOTE THAT GAS CAN BE SUBMITTED UNDER A SEPARATE |
| PERMIT BY REQUEST. |
| |
| 1) SHEET E-1 SHOWS A GAS FIRED TANKLESS WATER HEATER, |
| RANGE, AND DRYER IN THE PANEL SCHEDULE. THESE APPEAR TO |
| BE NEW INSTALLATIONS BECAUSE THERE ARE NO PREVIOUS GAS |
| PERMIT RECORDS ON FILE IN THE WPB BUILDING DEPT. PLEASE |
| SUBMIT COMPLETE GAS PLANS AND A GAS RISER DRAWING IN |
| COMPLIANCE WITH- SECS. 107.2.1 & 107.3.5.3 WPB. THE |
| RISER SHALL INCLUDE ALL NEW AND EXISTING GAS PIPING AND |
| APPLIANCES AT THE RESIDENCE- SEC. G2412.3 & G2412.4 FBC |
| RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS AND PROVIDE- |
| |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE |
| AND DRYER AND INDICATE HOW THE AIR WILL BE PROVIDED. - |
| SEC. G2407.1 FBC RES. PLEASE NOTE IF USING THE STANDARD |
| INDOOR AIR METHOD PER SEC. G2407.5.1 THE MINIMUM |
| REQUIRED VOLUME IS 50 CU.FT. PER 1000 BTUH. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |