Plan Review Notes
Plan Review Notes For Permit 23061098
Permit Number 23061098
Review Stop B
Sequence Number 1
Notes
Date Text
2023-07-27 18:16:27RESIDENTIAL(R3) SOLAR PANELS BUILDING AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23061098
 901 42ND ST
  
 1- THE ROOF PRESSURES SPECIFIED ON SHEET S-1 ARE TOO
 LOW FOR A BUILDING LOCATED IN EXPOSURE C.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE REVISED PRESSURES WITH CROSSRAIL
 SYSTEM STRUCTURAL EVALUATION ON SHEETS S-11 AND S-12.
  
 2- ROOF DIMENSION "A" NEEDS TO BE 4" NOT 3" AS REQUIRED
 BY NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. REVISE
 AS REQUIRED.
  
 3- SHEET S-2 SHOWS A "TYPICAL SHINGLE ROOF LAYOUT".
 ENGINEER OF RECORD NEEDS TO SHOW ROOF PLAN SHOWING
 SPECIFIC LOCATION OF MODULES AND SPECIFIC ANCHORING
 POINTS.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  