2023-07-18 10:10:16PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THAT THE PROPOSED PERMANENT LADDER WILL COMPLY
 WITH FBC 1011.16 LADDERS.PERMANENT LADDERS SHALL NOT
 SERVE AS A PART OF THE MEANS OF EGRESS FROM OCCUPIED
 SPACES WITHIN A BUILDING. PERMANENT LADDERS SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH SECTION 306.5 OF THE
 FLORIDA BUILDING CODE, MECHANICAL. FBC-M306.5 EQUIPMENT
 AND APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE
 EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON
 AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH
 THAT PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET
 (4877 MM) ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR
 APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
 SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES (762
 MM) IN HEIGHT OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE
 USE OF PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING
 OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE
 TOP OF THE PARAPET WALL.
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR ROOF
 EDGE NOT LESS THAN 30 INCHES (762 MM).
 LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 INCHES
 (356 MM) ON CENTER. THE UPPERMOST RUNG SHALL BE NOT
 GREATER THAN 24 INCHES (610 MM) BELOW THE UPPER EDGE OF
 THE ROOF HATCH, ROOF OR PARAPET, AS APPLICABLE.
 LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 INCHES
 (152 MM) DEEP.
 THERE SHALL BE NOT LESS THAN 18 INCHES (457 MM) BETWEEN
 RAILS.
 RUNGS SHALL HAVE A DIAMETER NOT LESS THAN 0.75-INCH (19
 MM) AND BE CAPABLE OF WITHSTANDING A 300-POUND (136.1
 KG) LOAD.
 LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 LANDING DIMENSIONS SHALL BE NOT LESS THAN 18 INCHES
 (457 MM) AND NOT LESS THAN THE WIDTH OF THE LADDER
 SERVED. A GUARD RAIL SHALL BE PROVIDED ON ALL OPEN
 SIDES OF THE LANDING.
 CLIMBING CLEARANCE. THE DISTANCE FROM THE CENTERLINE OF
 THE RUNGS TO THE NEAREST PERMANENT OBJECT ON THE
 CLIMBING SIDE OF THE LADDER SHALL BE NOT LESS THAN 30
 INCHES (762 MM) MEASURED PERPENDICULAR TO THE RUNGS.
 THIS DISTANCE SHALL BE MAINTAINED FROM THE POINT OF
 LADDER ACCESS TO THE BOTTOM OF THE ROOF HATCH. A
 MINIMUM CLEAR WIDTH OF 15 INCHES (381 MM) SHALL BE
 PROVIDED ON BOTH SIDES OF THE LADDER MEASURED FROM THE
 MIDPOINT OF AND PARALLEL WITH THE RUNGS EXCEPT WHERE
 CAGES OR WELLS ARE INSTALLED.
 LANDING REQUIRED. THE LADDER SHALL BE PROVIDED WITH A
 CLEAR AND UNOBSTRUCTED BOTTOM LANDING AREA HAVING A
 MINIMUM DIMENSION OF 30 INCHES (762 MM) BY 30 INCHES
 (762 MM) CENTERED IN FRONT OF THE LADDER.
 LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS.
 ACCESS TO LADDERS SHALL BE PROVIDED AT ALL TIMES.
  
 2) SPECIFY HOW THE LADDER WIL BE ABCHORED TO THE WALL.
 SPECIFY THE SPACING OF THE ANCHORS. THE TYPE OF ANCHORS
 AND THE EMBED DEPTH. THIS SHOULD BE CALCULATED BY AN
 ENGINEER. FBC 107.2.1.2
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  