Notes
Date Text
2023-07-03 08:46:31JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10450-R16
 HAS BEEN REVISED TO FL10450-R17. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGES; IT COVERS MULTIPLE
 PRODUCTS & INSTALLATION METHODS. SELECT PRODUCT &
 INSTALLATION METHOD TO BE USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS.
 2. SEC. 107.2.1.2 CITY AMENDMENTS. ROOF ZONES SPECIFIED
 ON THE CALCULATIONS SUBMITTED ARE INCORRECT. ARCHITECT
 NEEDS TO USE THE REVISED ZONES AND PROVIDE THE ZONES
 DIMENSIONS AS REQUIRED BY FIGURE R301.2(7)
 FBC-RESIDENTIAL OF CURRENT 2020 CODE.
 3. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ARCHITECT/ENGINEER; TO INCLUDE
 PROPOSED SYSTEM WITH PAGE NUMBER OF SYSTEM USED.
 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF
 HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  