Plan Review Notes
Plan Review Notes For Permit 23060976
Permit Number 23060976
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-29 14:37:02THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO SPECIFICATIONS OF THE MATERIAL OR
 STRUCTURE OF THE CANOPY SUBMIT WITH THE SITE PLAN, AND
 THESE MUST MEET THE FOLLOWING CODES FROM NFPA 13
 CHAPTER 8:
  
 8.15.7* EXTERIOR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE
 THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
 THAT
 ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE
 RETARDANT???
 TREATED WOOD AS DEFINED IN NFPA 703.
 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW
 THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION,
 PROVIDED
 THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS
 ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT???TREATED
 WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR
 PROJECTIONS CONTAIN
 ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE
 FOLLOWING
 UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE
 INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED
 TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE
 ENCLOSED
 JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME,
 INCLUDING
 SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR
 WITHIN
 THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC
 [SEE
 11.2.3.1.4(4)(D)]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS
 NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA
 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM
 EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE
 CORRIDOR
 ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS
 ENTIRELY
 OF NONCOMBUSTIBLE CONSTRUCTION.
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR
 PROJECTIONS
 GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE
 COMBUSTIBLES
 ARE STORED.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]