Plan Review Notes For Permit 23060976 |
Permit Number |
23060976 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-07 14:04:24 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE HEIGHT OF THE AWNING FRAME AND FABRIC | | ABOVE THE WALKWAY. FBC 3105.3.1.1 FABRIC AWNINGS AND | | FABRIC-COVERED FRAMES LOCATED OVER PUBLIC PROPERTY OR | | IN AREAS ACCESSIBLE TO THE GENERAL PUBLIC SHALL BE | | CONSTRUCTED SO THAT NO RIGID PART OF SUCH FABRIC | | AWNINGS OR FABRIC-COVERED FRAMES SHALL BE LESS THAN 7 | | FEET 6 INCHES (2286 MM) FROM THE GRADE DIRECTLY BELOW, | | AND NO PART OF THE CLOTH DROP SHALL BE LESS THAN 7 FEET | | (2134 MM). | | | | 2) SUBMIT TWO SETS OF DETAILED AWNING REMOVAL | | INSTRUCTIONS WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW | | THIS IS DONE IN TERMS THAT A LAYMAN WILL UNDERSTAND. | | THESE INSTRUCTIONS ARE TO BE PROVIDED TO THE PROPERTY | | OWNER, OWNER'S REPRESENTATIVE OR LESSEE. FBC 107.2.1 | | | | 3) SUBMIT THE FLAME SPREAD CERTIFICATE FOR THE AWNING | | FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR | | FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION | | PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD | | INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE | | WITH ASTM E84 OR UL 723. | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|