Plan Review Notes For Permit 23060934 |
Permit Number |
23060934 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-06-23 12:36:56 | FIRE COMMENT: | | | | TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13 | | | | CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION | | (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/ | | DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR | | LEAKS | | & INSPECTOR DRAIN AFTER 2 HRS) | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|