Plan Review Notes For Permit 23060872 |
Permit Number |
23060872 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-06-21 14:28:10 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL6267-R16 IS THE 2017 CODE VERSION AND IS NO | | LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020 | | CODE VERSION PRODUCT APPROVALS/NOA???S FOR THE PROPOSED | | ROOF RIDGE VENT SYSTEM TO BE USED. INCLUDE COVER PAGE, | | EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR | | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS | | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL | | DRAWINGS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|