Plan Review Notes
Plan Review Notes For Permit 23060842
Permit Number 23060842
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-22 16:20:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF INSTALL NEW TILE THROUGHT
 THE UNIT, HOWEVER, THERE IS NO TILE PRODUCT TYPE NOR
 NAME OR MANUFACTURER'S SPECIFICATION SHEET.
  
 TILE CAN HAVE DIFFERENT MEANINGS AND NEEDS TO BE
 CLARIFIED FOR THE OFFICIAL RECORD.
  
 TILE FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING TYPE, AND/OR PRODUCT NAME AND THE PRODUCT SPEC
 SHEETS INDICATING THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE ARE INDICATIONS OF WORK IN THE BATHROOMS THAT
 MAY INVOLVE THE TENANT FIRE RATED SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS ARE
 MAINTAINED & REPAIRED IF DAMAGED.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE
 PLAN SHEET.
  
  
  
 3) THERE ARE INDICATIONS OF WORK INVLOVING THE CEILING
 AND INTERIOR WALL SURFACES.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
 ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE
 CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP
 DRAWING BY FS/FA CONTRACTORS.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE
 PLAN SHEET.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  