2023-06-22 16:20:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF INSTALL NEW TILE THROUGHT |
| THE UNIT, HOWEVER, THERE IS NO TILE PRODUCT TYPE NOR |
| NAME OR MANUFACTURER'S SPECIFICATION SHEET. |
| |
| TILE CAN HAVE DIFFERENT MEANINGS AND NEEDS TO BE |
| CLARIFIED FOR THE OFFICIAL RECORD. |
| |
| TILE FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT |
| ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE |
| FLOORING TYPE, AND/OR PRODUCT NAME AND THE PRODUCT SPEC |
| SHEETS INDICATING THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF WORK IN THE BATHROOMS THAT |
| MAY INVOLVE THE TENANT FIRE RATED SEPARATION WALLS. |
| |
| ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS ARE |
| MAINTAINED & REPAIRED IF DAMAGED. |
| |
| PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE |
| PLAN SHEET. |
| |
| |
| |
| 3) THERE ARE INDICATIONS OF WORK INVLOVING THE CEILING |
| AND INTERIOR WALL SURFACES. |
| |
| PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| EQUIPMENT. |
| DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| DEVICES/EQUIPMENT. |
| THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| DEMO AND CONSTRUCTION. |
| ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE |
| CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP |
| DRAWING BY FS/FA CONTRACTORS. |
| |
| PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE |
| PLAN SHEET. |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |