2023-06-20 12:28:52 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL14317-R12 |
| HAS BEEN REVISED TO FL14317-R14. PLEASE PROVIDE A |
| COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF |
| COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT ALL |
| APPLICABLE OPTIONS FROM EACH CATEGORY. SELECT |
| ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.1 |
| DIRECT-TO-DECK PAGES #4 OR #5. SYSTEM SELECTED MUST |
| MEET OR EXCEED -78 MAXIMUM DESIGN PRESSURE. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| 2. FBC R 301 FAC9N-3. MECHANICAL TILE INSTALLATION. |
| PLEASE PROVIDE TABLE 3, PAGE #31 MECHANICAL FASTENING |
| FOR CONCRETE AND CLAY TILES OF THE FLORIDA HIGH WIND |
| CONCRETE AND CLAY TILE INSTALLATION MANUEL 6TH EDITION. |
| PLEASE INDICATE (HIGHLIGHT/CIRCLE) THE FOLLOWING: DECK |
| THICKNESS; METHOD; FASTENER TYPE; ATTACHMENT |
| DESCRIPTION; LOW, MEDIUM OR HIGH USING TABLE 2 HC PAGE |
| #26 OF THE FLORIDA HIGH WIND CONCRETE AND CLAY TILE |
| INSTALLATION MANUEL 6TH EDITION. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED. REQUIRED IF |
| THE MECHANICAL FASTENING RESISTANCE VALUES ARE NOT |
| LISTED IN THE PRODUCT APPROVAL/NOA. |
| 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| 4. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE TILE ADHESIVE TO BE USED. |
| 5. WPB A 109.3 BUILDING PERMIT VALUATIONS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES. VALUE TO INCLUDE LABOR AND |
| MATERIALS, ARCHITECTURAL AND DESIGN FEES, OVERHEAD AND |
| PROFIT. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |