Plan Review Notes
Plan Review Notes For Permit 23060804
Permit Number 23060804
Review Stop P
Sequence Number 1
Notes
Date Text
2023-07-15 12:07:391ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23060804
 7/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FDHA- FAIR HOUSING DESIGN ACT MANUAL- 1998
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1. GENERAL/ADMINISTRATIVE COMMENTS.
  
 1) POTABLE WATER SERVICE BACKFLOW PREVENTER & GREASE
 INTERCEPTORS: SEPARATE PERMITS ARE REQUIRED FOR THE
 POTABLE WATER BACKFLOW PREVENTER AND THE GREASE
 INTERCEPTORS- SEC. 105.1 & 107.2.1 WPB. PLEASE NOTE THE
 SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT BE
 APPROVED UNTIL PERMIT APPLICATIONS FOR THE ITEMS LISTED
 ABOVE HAVE BEEN SUBMITTED. YOU CAN SUBMIT APPLICATIONS
 TBD (TO BE DETERMINED) IF YOU DO NOT HAVE CONTRACTORS
 SELECTED BY EMAILING COMPLETED PERMIT APPLICATIONS TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE ALL
 OF THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 2) SWIMMING POOL: A SEPARATE PERMIT IS REQUIRED FOR THE
 POOL HOWEVER THE DETAIL ON SHEET P7-01 SHOWING POOL
 WASTEWATER DRAINING INTO THE SANITARY SYSTEM IS NOT IN
 COMPLIANCE WITH SEC. 90-126 (B)(5) WPB CODE OF
 ORDINANCES. PLEASE NOTE THE FOLLOWING INFORMATION.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 -THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 3) IRRIGATION: SEPARATE PERMITS ARE REQUIRED FOR THE
 IRRIGATION SYSTEM AND SYSTEM BACKFLOW PREVENTER. A
 PRELIMINARY REVIEW OF SHEETS L5 & L5-A SYSTEM WAS
 PERFORMED UNDER THIS MASTER PLAN AND THE PLANS APPEAR
 INCOMPLETE PER THE FOLLOWING NOTES:
  
 A) WATER SOURCES, PUMPS, SHUTOFF VALVES, AND BACKFLOW
 PREVENTERS NOT SHOWN.
  
 B) PIPING RUNS, PIPE SIZES AND LOCATIONS OF SLEEVES NOT
 PROVIDED
  
  
 2. ARCHITECTURAL COMMENTS.
  
 4) LS1-00: PLEASE REFER TO SEC. 233 FBC ACCESSIBILITY.
 BASED ON SECS 233.3.1 & 233.3.1.1 AT LEAST 5% OF THE
 TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL BE
 PROVIDED WITH MOBILITY FEATURES COMPLYING WITH SECS.
 809.2- 809.4 AND SHALL BE ON AN ACCESSIBLE ROUTE; AND
 AT LEAST 2% SHALL BE PROVIDED WITH COMMUNICATION
 FEATURES COMPLYING WITH 809.4. THESE REQUIREMENTS ARE
 SEPARATE FROM COMPLIANCE WITH THE FAIR HOUSING DESIGN
 ACT REQUIREMENTS. REFER TO SEC. 233.3.5 DISPERSION AND
 PROVIDE A LIST OR SCHEDULE ON THE PLAN SHOWING THE
 LOCATIONS OF THE UNITS, AND REVISE THE ARCHITECTURAL
 AND PLUMBING PLANS WHERE REQUIRED.
  
 5) LS1-00, A6-35: THE APPLICABLE CODE DATA FOR THE
 BUILDING INDICATES THE R2 APARTMENT UNITS ARE DESIGNED
 IN ACCORDANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL
 (1998). REFER TO PAGES 7.34 & 7.35 OF THE MANUAL AND
 INDICATE ON BOTH PLANS WHICH DESIGN SPECIFICATION FOR
 THE APARTMENT BATHROOMS AND FIXTURES INSTALLATIONS HAS
 BEEN CHOSEN- SPECIFICATION A OR B.
  
 A) A7-04: PLEASE ADD COMPLIANCE DETAILS FOR THE
 SHOWERS- PAGES 7.56- 7.59 FHDA MANUAL.
  
 6) LS1-00: AS NOTED IN COMMENT #4 THERE ARE DESIGN
 DIFFERENCES BETWEEN AN FBC ACCESSIBLE (ADA COMPLIANT)
 DWELLING UNIT AND A FHDA COMPLIANT UNITS HOWEVER SHEETS
 A6-35 & A7-04 WHICH ARE INTENDED TO DEMONSTRATE FAIR
 HOUSING COMPLIANCE ARE TITLED ENLARGED UNIT
 ACCESSIBILITY PLANS & APARTMENT UNIT ACCESSIBILITY
 STANDARDS WHICH CAN BE MISLEADING. PLEASE REFER TO SEC.
 809.4 FBC ACCESSIBILITY AND PROVIDE SEPARATE ENLARGED
 ACCESSIBLE UNIT DRAWINGS WITH THE FOLLOWING COMPLIANCE
 DETAILS PER SEC. 603- 610 FBC ACCESSIBILITY. PLEASE
 NOTE SOME OF THE REQUIRED DETAILS ARE CURRENTLY SHOWN
 ON A7-05.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
  
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
  
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
  
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SEC. 606.3.
  
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3.
  
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
  
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
  
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 K) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 BATHTUBS- SEC. 607.2.
  
 L) BATHTUB PERMANENT OR REMOVAL SEAT DETAILS- SEC.
 607.3.
  
 M) BATHTUB GRAB BAR DETAILS- SEC. 607.4.
  
 N) BATHTUB CONTROLS DETAILS- SECS. 607.5- 607.6.
  
 O) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SHOWER- SECS. 608.2.1 & 608.2.2.
  
 P) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 AND
 608.3.2.
  
 Q) LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS IN
 THE SHOWERS- SECS. 608.5.1 & 608.5.2.
  
 R) LOCATIONS OF ACCESSIBLE SHOWER SEATS AND MOUNTING
 DETAILS- SECS. 610.3- 610.4.
  
 7) A6.05: SHOW THE DIMENSIONS OF THE WATER CLOSET AND
 LAVATORY CLEAR FLOOR SPACES- SECS. 604.3 & 606.2 FBC
 ACC.
  
 8) A6.05: THE RESTROOM DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACES FOR THE LAVATORIES- SEC. 603.2.3 FBC
 ACC.
  
 9) A1-01A: ENLARGED ACCESSIBLE PUBLIC RESTROOM FLOOR
 PLAN DRAWINGS NOT PROVIDED- SEC. 603- 604 FBC ACC.
  
 10) LS1-00: PLUMBING FIXTURE CALCULATIONS FOR THE MIXED
 OCCUPANCY BUILDING ARE REQUIRED IN COMPLIANCE WITH
 TABLE 403.1 & SEC. 403.1.1 FBC P. PLEASE PROVIDE A
 SCHEDULE THAT ITEMIZES THE REQUIRED AND PROVIDED NUMBER
 OF FIXTURES. PLEASE NOTE THAT WHERE DRINKING FOUNTAINS
 ARE REQUIRED A MINIMUM OF TWO- ONE HI AND ONE LO- SHALL
 BE PROVIDED- SEC. 410.3 FBC P. THE ARCHITECTURAL AND
 PLUMBING PLANS SHOW ONE DRINKING FOUNTAIN AT THE PUBLIC
 RESTROOMS WHICH DOES NOT MEET COMPLIANCE UNLESS THE
 FOUNTAIN MEETS EXCEPTION 1 AND HAS TWO SEPARATE SPOUTS-
 HI & LO. NO FOUNTAIN WAS SPECIFIED IN THE FIXTURE
 SCHEDULES- SHEET P0-02.
  
 A) A1-01B: THE DRINKING FOUNTAIN AT THE PUBLIC RESTROOM
 CORRIDOR IS PROTRUDING INTO THE CIRCULATION PATH AND
 SHALL BE EITHER BE RECESSED IN A NICHE OR BARRIERS ON
 EACH SIDE SHALL BE PROVIDED- SEC. 307.2 FBC ACC.
  
 B) A1-01B: PLEASE SHOW THE CLEAR FLOOR DIAGRAM AND
 DIMENSIONS FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN
 POSITIONED FOR A FORWARD APPROACH- SEC. 606.2 FBC ACC.
  
 C) A7-05: SHOW THE SPOUT HEIGHT FOR THE HI (STANDING
 PERSONS) DRINKING FOUNTAIN- SEC. 602.7 FBC ACC.
  
 11) LS-01, A1-05B & A6-06: THE POOL WILL BE UNDER
 SEPARATE PERMIT HOWEVER A PRELIMINARY REVIEW OF THE
 POOL BATHROOMS AND PLUMBING IS REQUIRED. PLEASE REFER
 TO SEC. & TABLE 403.6 AND PROVIDE PLUMBING FIXTURE
 CALCULATIONS. THE PLANS SHOW ONE POOL RESTROOM BY THE
 POOL AND ONE RESTROOM AT THE CLUB ROOM. PLEASE NOTE
 THAT SEC. 451.6.1 STATES THAT POOLS WITH A BATHING LOAD
 OF 20 PERSONS OR LESS MAY UTILIZE A UNISEX RESTROOM.
 PLEASE PROVIDE BATHING LOAD CALCULATIONS IN ACCORDANCE
 WITH SEC. 454.1.1.1 FBC B.
  
 B) PLEASE REFER TO SEC. 403.6 AND PROVIDE A URINAL AND
 DIAPER CHANGING TABLE FOR THE POOL BATHROOM. A FLOOR
 DRAINS AND HOSE BIB ARE ALSO REQUIRED FOR THE BATHROOMS
 ACCORDING TO SECS. 454.1.6.1.3 & 454.1.6.1.4 FBC
 BUILDING. PLEASE NOTE THE HOSE BIB CAN BE PROVIDED IN
 OR WITHIN 25 FT. OF THE RESTROOM. PLEASE REVISE THE
 PLANS TO SHOW COMPLIANCE.
  
 C) PLEASE SHOW THE POOL SHOWER LOCATION- SEC. 454.1.6.2
 FBC B.
  
 12) LS-01, A1-05B & A6-06: CONCERNING THE CLUBROOM AND
 ROOFTOP LOUNGE REFER TO COMMENT #10.
  
 13) A1-05B: THE POOL RESTROOM DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY- SEC. 603.2.3
 FBC ACC.
  
 14) A1-01B & A7.05: SHOW THE CLEAR FLOOR SPACE FOR THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN AND THE SPOUT
 HEIGHT OF THE HI (STANDING PERSONS) FOUNTAIN- SEC.
 602.2 & 602.7 FBC ACC.
  
 3. PLUMBING COMMENTS.
  
 15) P2-00A: TWO-WAY CLEANOUTS FOR THE 3 & 4-INCH
 BUILDING DRAINS ARE REQUIRED AT A POINT 30 INCHES
 BEYOND THE EXTERIOR WALL OF EACH UNIT- SEC. 708.1.3,
 708.1.8 EXCEPTION 2 FBC P.
  
 16) P2-00A & P2-00B: IT APPEARS CLEANOUTS AT 100 FT.
 INTERVAL SPACINGS ARE MISSING FOR THE 6-INCH SANITARY
 SEWER LINE ON THE NORTH SIDE OF THE BUILDING- SEC.
 708.1.2 FBC P.
  
 17) P2-00A & P-200B: PROVIDE A GROUND FLOOR SANITARY
 DRAINAGE AND VENT ISOMETRIC FOR THE GROUND FLOOR WITH
 WASTE AND SOIL STACK RISER LOCATIONS NUMBERED TO MATCH
 WITH THE NUMBERED RISERS SHOWN ON SHEETS P6-02 & P6-03-
 SECS. 107.2.1, 107.3.5.1.3 WPB & SEC. 710.1 FBC P.
  
 18) P2-00A: SHOW UNDERGROUND STORM DRAIN PIPING RUNS
 INCLUDING PIPE SIZES AND GPM FLOWS AS SHOWN ON P-200B-
 SEC. 1106.2 FBC P.
  
 19) P2-00A & P-200B: SHOW THE WATER HEATER DRAIN PAN
 LINE RUNS AND TERMINATION LOCATIONS- SEC. 504.7.2 FBC
 P.
  
 20) P2-00A, P2-00B, P2-09A, P2-09B: PROVIDE A STORM
 DRAIN RISER DRAWING SHOWING VERTICAL AND HORIZONTAL
 PIPE RUNS AND SIZES FROM ROOFTOP TO DISPOSAL LOCATIONS-
 SEC. 1106.2 & 1106.3 FBC P. PLEASE INCLUDE GPM FLOWS,
 CLEANOUT LOCATIONS AND AC CONDENSATE PIPING POINTS OF
 CONNECTIONS TO THE SYSTEM- SECS. 314.2.1, 1101.8 FBC P.
  
 21) P2-00A, P2-00B & C2-3: THE PLUMBING UNDERGROUND
 PLANS DO NOT MATCH WITH THE WATER AND WASTEWATER CIVIL
 PLAN. THE PLUMBING PLANS DO NOT SHOW SANITARY DRAIN
 CONNECTIONS INTO TEMPORARY LIFT STATIONS, AND THE CIVIL
 PLANS DO NOT SHOW THE GREASE INTERCEPTORS, OR THE
 SANITARY SER LINE ON THE NORTH SIDE OF THE BUILDING TO
 NAME A FEW OF THE MANY INCONSISTENCIES- SEC. 107.2.1
 WPB. PLEASE CORRECT THE PLANS. AT THIS TIME THE CIVIL
 PLANS WILL BE EXCLUDED FROM FURTHER PLUMBING REVIEW.
  
 22) P0-02 & P2-00B & GREASE INTERCEPTORS GI-1.
  
 A) P2-00B & P7-01: THE CLEANOUTS FOR THE GREASE
 INTERCEPTORS REQUIRE HEAVY DUTY TRAFFIC LIDS. PLEASE
 SPECIFY MAKES AND MODELS- SEC. 305.7 FBC P.
  
 B) P0-02: THE INTERCEPTOR EQUIPMENT SCHEDULE REFERS TO
 SHEET P-702 WHICH WAS NOT INCLUDED WITH THE UPLOADED
 PLAN SET- SEC. 107.2.1 WPB.
  
 C) P2-00B: THE PLAN DOES NOT IDENTIFY WHICH PLUMBING
 FIXTURES AND APPLIANCES ARE DISCHARGING INTO THE GREASE
 WASTE LINE. PLEASE PROVIDE A KITCHEN PLUMBING FIXTURE
 EQUIPMENT PLAN AND SCHEDULE- SEC. 107.2.1 WPB. PLEASE
 NOTE THE PLAN APPEARS TO SHOW DRAINAGE FROM A
 3-COMPARTMENT SINK AND A MOP SINK DISCHARGING INTO THE
 SANITARY LINE INSTEAD OF THE GREASE WASTE LINE- SEC.
 1003.3.1 FBC P.
 D) P2-00B: REFER TO SEC. 1003.9 FBC P AND PROVIDE
 VENTING FOR THE INTERCEPTOR. PLEASE NOTE THE AAV (NOTE
 2) CANNOT BE USED AS THE VENT FOR THE INTERCEPTORS-
 SEC. 918.8 FBC P.
  
 23) P2-00B GREASE INTERCEPTOR GI-2: THE USE OF THE
 GREASE INTERCEPTOR FOR TRASH ROOM DRAINAGE DOES NOT
 APPEAR TO BE IN COMPLIANCE WITH SEC. 1003.3.1 FBC P.
 PLEASE CLARIFY THE USE OF THE INTERCEPTOR.
  
 A) PROVIDE SIZING CALCULATIONS IN ACCORDANCE WITH SEC.
 1003.3.5 FBC P.
  
 B) P2-00B & P7-01: THE CLEANOUTS FOR THE GREASE
 INTERCEPTORS REQUIRE HEAVY DUTY TRAFFIC LIDS. PLEASE
 SPECIFY MAKES AND MODELS- SEC. 305.7 FBC P.
  
 C) P2-00B: REFER TO SEC. 1003.9 FBC P AND PROVIDE
 VENTING FOR THE INTERCEPTOR. PLEASE NOTE THE AAV (NOTE
 2) CANNOT BE USED AS THE VENT FOR THE INTERCEPTORS-
 SEC. 918.8 FBC P.
  
 24) P2-00B & P5-01: THE DISCHARGES FROM THE ELEVATOR
 SUMP PUMPS SHALL BE INDIRECTLY CONNECTED TO A WASTE
 RECEPTOR WHICH IS EITHER A FLOOR DRAIN, FLOOR SINK, HUB
 DRAIN OR STANDPIPE. DISPOSAL AT THE MOP SINK IS NOT IN
 COMPLIANCE - SEC. 3002.4 FBC B, & SECS. 202 & 802.3 FBC
 P.
  
 25) P2-01A & P2-01B: PROVIDE A FIRST-FLOOR WATER
 ISOMETRIC DRAWING WITH WATER RISER LOCATIONS NUMBERED
 TO MATCH WITH THE NUMBERED RISERS SHOWN ON SHEET P6-01-
 SECS. 107.2.1, 107.3.5.1.3 WPB & SEC. 604.1 FBC P.
  
 26) P2-01B: SHOW THE WATER SERVICE ENTRANCE LOCATION
 AND MAIN SHUTOFF VALVE FOR THE BUILDING- SEC. 603.1-
 603.2.1 & 606.1 FBC P.
  
 27) P2-01B: SHOW THE WATER FEED LINE TO THE RETAIL
 RESTROOMS AT DETAIL 4/P5.01- SEC. 107.2.1 WPB.
  
 28) P2-01B: PLEASE PROVIDE WATER DISTRIBUTION DESIGN
 CRITERIA- SEC. 604.3 FBC P.
  
 29) P4-01: ENLARGED SANITARY DRAINAGE/VENT AND WATER
 RISER DRAWINGS NOT PROVIDED FOR THE TYPICAL APARTMENT
 UNITS- SEC. 107.3.5.1.3 WPB.
  
 30) P4-01: TWO-WAY CLEANOUTS FOR THE 3 & 4-INCH
 BUILDING DRAINS ARE REQUIRED AT A POINT 30 INCHES
 BEYOND THE EXTERIOR WALL OF EACH UNIT- SEC. 708.1.3,
 708.1.8 EXCEPTION 2 FBC P.
  
 31) P2-08B, P5-01: ENLARGED SANITARY DRAINAGE/VENT
 PLANS FOR THE POOL AND CLUBROOM/ROOFTOP LOUNGE
 RESTROOMS NOT PROVIDED- SEC. 107.3.5.1.3 WPB.
  
 32) P5-01: ENLARGED SANITARY DRAINAGE/VENT AND WATER
 ISOMETRIC DRAWINGS NOT PROVIDED FOR THE 1ST FLOOR
 PUBLIC, RETAIL, POOL AND CLUBROOM/LOUNGE BATHROOMS-
 SEC. 107.3.5.1.3 WPB.
  
 33) P5-01: COLD OR TEMPERED WATER SHALL BE DELIVERED
 FROM THE LAVATORIES- SEC. 419.5.
  
 34) P5.01: THE 1/2-INCH HOT WATER FIXTURE SUPPLY PIPES
 TO THE RETAIL RESTROOM LAVATORIES ARE EXCEEDING THE
 MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER
 SOURCES- TABLE C404.5.1 FBC ENERGY.
  
 35) P4-01 & P5-01: A MEANS OF LIMITING THE TEMPERATURE
 OF THE HOT WATER DELIVERY TO THE FIXTURES IS REQUIRED
 OTHER THAN THE WATER HEATER THERMOSTAT- SEC. 607.1.1
 FBC P. PLEASE PROVIDE MASTER THERMOSTATIC MIXING
 VALVES.
  
 36) P6-02 & P6-03: THE VENT STACKS SHALL CONNECT TO THE
 BASES OF THE DRAINAGE STACKS AT A POINT BELOW THE
 LOWEST HORIZONTAL BRANCH. CONNECTIONS AT THE LAVATORY
 DRAINS DO NOT MEET COMPLIANCE- SECS. 904.2 & 904.4 FBC
 P.
  
 37) P2-09A, P2-09B: AS PREVIOUSLY NOTED IN COMMENT #10
 A STORM RISER ISOMETRIC DRAWING IS REQUIRED- SEC.
 107.3.5.1.3 WPB.
  
 A) P2-09A, P2-09B: SECONDARY/EMERGENCY ROOF DRAINAGE
 WILL BE HANDLED BY OVERFLOW SCUPPERS AS STATED IN NOTE
 B. THE LOCATIONS OF THE SCUPPERS SHALL BE SHOWN ON THE
 PLANS, AND A CONSTRUCTION DETAIL SHOWING THE SCUPPER
 OPENING DIMENSIONS, AND HEIGHT ABOVE ROOF ETC. SHALL BE
 PROVIDED- SECS. 1108.1- 1108.3 FBC P.
  
 38) P0-01: PLUMBING FIXTURE CALCULATIONS FOR THE MIXED
 OCCUPANCY BUILDING ARE REQUIRED IN COMPLIANCE WITH
 TABLE 403.1 & SEC. 403.1.1 FBC P. PLEASE PROVIDE A
 SCHEDULE THAT ITEMIZES THE REQUIRED AND PROVIDED NUMBER
 OF FIXTURES. PLEASE NOTE THAT WHERE DRINKING FOUNTAINS
 ARE REQUIRED A MINIMUM OF TWO- ONE HI AND ONE LO- SHALL
 BE PROVIDED- SEC. 410.3 FBC P. THE ARCHITECTURAL AND
 PLUMBING PLANS SHOW ONE DRINKING FOUNTAIN AT THE PUBLIC
 RESTROOMS WHICH DOES NOT MEET COMPLIANCE UNLESS THE
 FOUNTAIN MEETS EXCEPTION 1 AND HAS TWO SEPARATE SPOUTS-
 HI & LO. NO FOUNTAIN WAS SPECIFIED ON SHEET P0-02.
  
 39) P0-01, P2-08B: THE POOL WILL BE UNDER SEPARATE
 PERMIT HOWEVER A PRELIMINARY REVIEW OF THE POOL
 BATHROOMS AND PLUMBING IS REQUIRED. PLEASE REFER TO
 SEC. 403.6 AND PROVIDE A URINAL AND DIAPER CHANGING
 TABLE FOR EACH POOL BATHROOM. FLOOR DRAINS AND HOSE
 BIBS ARE ALSO REQUIRED FOR THE BATHROOMS ACCORDING TO
 SECS. 454.1.6.1.3 & 454.1.6.1.4 FBC BUILDING. PLEASE
 NOTE THE HOSE BIB CAN BE PROVIDED IN OR WITHIN 25 FT.
 OF EACH RESTROOM. PLEASE REVISE THE PLANS TO SHOW
 COMPLIANCE.
  
 40) P2-08B, P6-01, P6-02, P-6-03: PROVIDE PLUMBING
 PLANS AND RISERS FOR THE POOL AND CLUBHOUSE RESTROOMS
 AND THE BAR SINK- SEC. 107.2.1 & SEC. 107.3.5.1.3 WPB.
  
 41) P0-01: PLEASE PROVIDE TESTED AND APPROVED
 FIRESTOPPING ASSEMBLIES FOR PLUMBING PIPES PENETRATING
 FIRE-RATED WALLS AND FLOORS- SEC. 315.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  