Plan Review Notes For Permit 23060804 |
Permit Number |
23060804 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-17 17:07:12 | PLAN DENIED | | 1) PAGE M2-01B SHOWS EXHAUST DISCHARGEING IN TO THE | | GARAGE. REFER TO SECTION 501.3 EXHAUST DISCHARGE | | 2020 FBC (M) | | 2) PAGE M4-01 OUT DOOR AIR REQUIRE A CLASS ONE | | MOTORIZED DAMPER. | | SECTION 403.2.4.3 SHUTOFF DAMPER 2020 FLORIDA ENERGY | | CODE. | | 3) PLEASE PEOVIDE A COPY OF THE CLOTHES DRYER | | MANUFACTURE | | SPECIFICATIONS. SECTION 504.8.4.1 SPECIFIED LENGTH. | | 2020 FBC (M) | | 4) PROVIDE FRESH AIR CALCULATIONS FOR THE AMANITYS AREA | | ON THE FIRST FLOOR TABLE 403.3.1.1 FBC (M) 2020. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|