Date |
Text |
2023-07-17 12:20:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) LIFE SAFETY & ELECTRICAL SHEETS - THERE APPEARS TO |
| BE DISCREPANCIES OF EXIT SIGNS MARKING THE TRAVEL PATHS |
| LEADING TO AN EXIT. |
| |
| PER NFPA 101 CH 7 MEANS OF EGRESS |
| |
| 7.10.1 GENERAL. |
| 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| MARKED IN ACCORDANCE |
| WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS 11 THROUGH |
| 43. |
| 7.10.1.2 EXITS. |
| 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| THAT OBVIOUSLY |
| AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| BY AN APPROVED |
| SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| ACCESS |
| |
| 7.10.1.5 EXIT ACCESS. |
| 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| READILY VISIBLE |
| SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| EXIT IS NOT READILY |
| APPARENT TO THE OCCUPANTS. |
| 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO |
| POINT IN AN EXIT |
| ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING |
| DISTANCE OR 100 FT (30 M), |
| WHICHEVER IS LESS, FROM THE NEAREST SIGN |
| |
| ENSURE EXIT TRAVEL PATHS IS MARKED WITH EXIT SIGNS PER |
| NFPA 101 CH 7 ON BOTH THE LIFE SAFETY & ELECTRICAL |
| PLANS. |
| |
| 2) FIRE ALARM DOCUMENTATION - THERE ARE INDICATIONS OF |
| FIRE ALARM DEVICES/EQUIPMENT ON ELECTRICAL SHEET, |
| HOWEVER, THERE DOES NOT APPEAR TO BE FIRE ALARM |
| DOCUMENTATION IN COMPLIANCE WITH F.A.C. 61G |
| |
| PER F.A.C. |
| |
| 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| ENGINEERING |
| DOCUMENTS. |
| (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| AND STANDARDS, WHERE AVAILABLE. |
| (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENTS. |
| (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENTS. |
| (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| IN UNDERSTANDING THE OWNER???S INTENDED USE AND |
| PROPOSED PROTECTION OF THE BUILDING OR FACILITY AND TO |
| PROVIDE SUFFICIENT DIRECTION TO THE INSTALLATION |
| CONTRACTOR OR OTHER INTERESTED PARTIES REGARDING THE |
| LAYOUT OF THE SYSTEM(S), SHALL BE INCLUDED IN THE FIRE |
| PROTECTION SYSTEM ENGINEERING DOCUMENTS. |
| |
| |
| 61G15-32.008 DESIGN OF FIRE ALARMS AND DETECTION |
| SYSTEMS. |
| (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE |
| PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS, |
| ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE |
| SIGNALING OF EMERGENCY CONDITIONS. |
| (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE |
| FLORIDA BUILDING CODE (2007), THE FLORIDA FIRE |
| PREVENTION CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY |
| HAVING JURISDICTION. |
| (3) FOR FIRE ALARM PLANS ON SMALL SYSTEMS BELOW THE |
| THRESHOLD REQUIREMENTS FOR MANDATORY USE OF |
| PROFESSIONAL ENGINEERING SERVICES, THE ENGINEER OF |
| RECORD SHALL SPECIFY THE MINIMUM SYSTEM REQUIREMENTS. |
| (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND |
| DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS |
| SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION |
| WHEN APPLICABLE: |
| (A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND, |
| SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND |
| NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. |
| INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS |
| DETERMINED BY THE SYSTEM???S SURVIVABILITY |
| REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE |
| PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS |
| IT IS CLEAR FROM FEATURES SHOWN. |
| (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND |
| CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND |
| SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS |
| INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS, |
| DAMPERS, AND DOORS. |
| (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL |
| NOTIFICATION DEVICES. |
| (D) IDENTIFY THE CLASS AND STYLE OF CIRCUITS AS LISTED |
| IN THE NFPA 72. |
| (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND |
| CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY |
| SIGNALS BEING MONITORED OR ANNUNCIATED. |
| (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR |
| ADDRESSABLE, AND INDICATE ALL ZONING. |
| (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED |
| PROTECTIVE FEATURES. |
| (H) LOCATE SYSTEM DEVICES THAT ARE SUBJECT TO |
| ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR |
| THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY |
| OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR. |
| (I) THE PLANS SHALL INCLUDE A SITE PLAN OF THE |
| IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE |
| OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE |
| THE STRUCTURE. |
| (J) IN BUILDINGS WERE SMOKE DETECTION WILL BE |
| OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE |
| ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND |
| DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE |
| OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A |
| PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH |
| AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE |
| ENGINEERING DESIGN DOCUMENTS. |
| (K) FIRE DETECTION SYSTEMS UTILIZING SMOKE DETECTION IN |
| SITUATIONS WHERE SMOKE STRATIFICATION IS ANTICIPATED, |
| THE DESIGN SHALL PROVIDE THE NECESSARY CRITERIA TO |
| MITIGATE THE DETECTION PROBLEMS. |
| (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA |
| SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR |
| STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING |
| JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE |
| FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING |
| CODE (2007). |
| (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO |
| PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED |
| EVACUATION FOR ALL HIGH-RISE BUILDINGS OR |
| MULTI-TENANTED PROPERTIES AS DEFINED IN THE FLORIDA |
| BUILDING CODE (2007). |
| (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS, |
| CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND |
| BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE |
| ENGINEERING DESIGN DOCUMENTS. |
| (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE |
| PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND |
| INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED |
| TO OPERATE THE SYSTEMS AS INTENDED OVER TIME. |
| (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO |
| SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED |
| WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS) |
| CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL |
| BE COMPLETED USING THE EQUIPMENT MANUFACTURE???S DATA |
| AND APPLICABLE NFPA 72 PROCEDURES. |
| (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE |
| ENGINEERING DESIGN DOCUMENTS. |
| (7) WHEN THE ENGINEER DETERMINES THAT SPECIAL |
| REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE |
| UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE |
| REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE |
| ENGINEERING DESIGN DOCUMENTS. |
| |
| EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR, |
| THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G |
| INFORMATION WITH THIS MASTER. |
| |
| PLEASE PROVIDE THE REQUIRED DOCUMENTATION. |
| |
| |
| 3) SHEET E 1-01 & FA 01A - THERE APPEARS TO BE |
| INDICATIONS OF A FIRE PUMP, HOWEVER, THERE IS NO |
| INDICATION OF THE FIRE PUMP EMERGENCY BACK-UP POWER NOR |
| ITS FUEL SUPPLY. |
| |
| |
| PER NFPA 101 CH 11 |
| |
| 11.8.5 EMERGENCY AND STANDBY POWER. |
| 11.8.5.1 EMERGENCY POWER REQUIREMENTS FOR ELECTRIC FIRE |
| PUMPS SHALL |
| BE IN ACCORDANCE WITH NFPA 20. |
| 11.8.5.2 EMERGENCY POWER REQUIREMENTS FOR DETECTION, |
| ALARM, AND COMMUNICATIONS |
| SYSTEMS SHALL BE IN ACCORDANCE WITH NFPA 72. |
| 11.8.5.3 REQUIREMENTS FOR STANDBY POWER SHALL BE AS |
| SPECIFIED IN |
| 11.8.5.3.1 THROUGH 11.8.5.3. |
| 11.8.5.3.1 TYPE 60, CLASS 1, LEVEL 1, STANDBY POWER IN |
| ACCORDANCE WITH |
| NFPA 110 SHALL BE PROVIDED. |
| 11.8.5.3.2 THE STANDBY POWER SYSTEM SHALL HAVE A |
| CAPACITY AND RATING |
| SUFFICIENT TO SUPPLY ALL REQUIRED EQUIPMENT. |
| 11.8.5.3.3 SELECTIVE LOAD PICKUP AND LOAD SHEDDING |
| SHALL BE PERMITTED |
| IN ACCORDANCE WITH NFPA 70. |
| 11.8.5.3.4 THE STANDBY POWER SYSTEM SHALL BE CONNECTED |
| TO THE |
| FOLLOWING: |
| (1) JOCKEY PUMP, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2 |
| FOR SPECIAL PURPOSE |
| INDUSTRIAL OCCUPANCIES |
| (2) AIR COMPRESSOR SERVING DRY-PIPE AND PRE-ACTION |
| SYSTEMS, EXCEPT |
| AS OTHERWISE PROVIDED IN 40.4.2 FOR SPECIAL-PURPOSE |
| INDUSTRIAL |
| OCCUPANCIES |
| (3) EMERGENCY COMMAND CENTER EQUIPMENT AND LIGHTING |
| (4) NOT LESS THAN ONE ELEVATOR SERVING ALL FLOORS, WITH |
| STANDBY POWER |
| TRANSFERABLE TO ANY ELEVATOR |
| (5) MECHANICAL EQUIPMENT FOR SMOKEPROOF ENCLOSURES |
| (6) MECHANICAL EQUIPMENT REQUIRED TO CONFORM WITH THE |
| REQUIREMENTS |
| OF SECTION 9.3 |
| (7) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| 11.8.8 |
| |
| PER NFPA |
| |
| NFPA 101 CHAPTER 7 SECTION 7.9 |
| |
| 7.9.1 FUEL TANKS SHALL BE SIZED TO ACCOMMODATE THE |
| SPECIFIC |
| |
| EPS CLASS. |
| |
| 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| AND MAINTAINED |
| IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| 54, NATIONAL |
| FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| CODE. |
| |
| |
| PLEASE PROVIDE DETAILS AND CONFIRMATION OF THE |
| REQUIREMENTS. |
| |
| |
| 4) THERE ARE NO INDICATIONS OF COMPLIANCE WITH THE |
| REQUIREMENTS OF EMERGENCY RADIO COMMUNICATIONS |
| |
| TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. |
| NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| RADIO ENHANCEMENT SERVICES. |
| 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| DETERMINED BY THE AHJ. |
| NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| SYSTEMS. |
| 24.9.1 GENERAL. |
| 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| CAPABLE |
| OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| FREQUENCIES |
| ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| INSTALLED |
| WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| AUTHORITY |
| HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| DEGRADE |
| THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED |
| FOR |
| APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| SUCCESSFUL |
| ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| FOR THE |
| PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| BY |
| THE AUTHORITY HAVING JURISDICTION. |
| |
| THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH |
| FIRE DEPARTMENT. |
| |
| TESTING SHALL BE BY AN ACCEPTABLE NATIONAL STANDARD |
| DOCUMENTING PERCENTAGES NOTED ABOVE AND BY ACTUAL RADIO |
| TESTING BY FIRE PERSONNEL. |
| |
| IF THE MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL |
| AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM |
| 2-HOUR RUN TIME BATTERY BACK-UP. |
| |
| CONTACT SHALL BE MADE TO KEN DECKER, PALM BEACH COUNTY |
| PUBLIC SAFETY RADIO SYSTEMS MANAGER, |
| [email protected], 561-233-0837; AS OUR RADIOS OPERATE |
| ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| INSTALLATION INSTRUCTIONS. |
| |
| NO PERMIT SHALL BE SUBMITTED OR BDA SYSTEM INSTALLED |
| UNTIL ALL DOCUMENTATION IS REVIEWED BY PBC & THE OFFICE |
| OF THE FIRE MARSHAL AND SUBSEQUENTLY APPROVED FOR |
| INSTALL OR PARTIAL INSTALL. |
| |
| PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE |
| ON THE LIFE SAFETY PLAN SHEETS. |
| |
| |
| |
| 5) SHEET LS1-01 & STRUCTURAL SHEETS - THERE IS AN |
| INDICATION OF A DOUBLE DOOR WITH DOOR OPENING OUT IN |
| THE DIRECTION OF EGRESS, HOWEVER, THERE APPEARS TO BE A |
| GATE/DOOR THAT OPENS IN AGAINST THE DIRECTION OF |
| EGRESS. |
| |
| PER NFPA 101 CH 7 MEANS OF EGRESS |
| |
| 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| REQUIRED TO BE OF |
| THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| THE DIRECTION |
| OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| OF 50 OR MORE, |
| EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| REQUIRED TO SWING |
| IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| 7.2.4.3.8.1 |
| OR 7.2.4.3.8.2. |
| (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| TO SWING |
| IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| CARE OCCUPANCIES, |
| AS PROVIDED IN CHAPTER 19. |
| (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| ENCLOSURE, UNLESS THE |
| DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| OPENS DIRECTLY |
| INTO AN EXIT ENCLOSURE |
| (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| CONTENTS AREA |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 5A) IN ADDITION TO THE ABOVE, THE EGRESS CAPACITY WIDTH |
| OF THE GATE/DOOR IS REDCUED FROM THE DOULBLE DOOR AND |
| MAY NOT PROVIDE SUFFICIENT EXIT WIDTH FOR THE OCCUPANY |
| LOAD. |
| |
| PER NFPA 101 CH 7 MEANS OF EGRESS |
| |
| 7.2.1.2.2* MEASUREMENT OF EGRESS CAPACITY WIDTH. |
| |
| 7.2.1.2.2.1 SWINGING DOOR ASSEMBLIES. FOR SWINGING DOOR |
| ASSEMBLIES, |
| EGRESS CAPACITY WIDTH SHALL BE MEASURED AS FOLLOWS: |
| (1) THE MEASUREMENT SHALL BE TAKEN AT THE NARROWEST |
| POINT IN THE DOOR |
| OPENING. |
| (2) THE MEASUREMENT SHALL BE TAKEN BETWEEN THE FACE OF |
| THE DOOR LEAF |
| AND THE STOP OF THE FRAME |
| (3) FOR NEW SWINGING DOORS ASSEMBLIES, THE MEASUREMENT |
| SHALL BE |
| TAKEN WITH THE DOOR LEAF OPEN 90 DEGREES. |
| (4) FOR ANY EXISTING DOOR ASSEMBLY, THE MEASUREMENT |
| SHALL BE TAKEN |
| WITH THE DOOR LEAF IN THE FULLY OPEN POSITION. |
| (5) PROJECTIONS NOT MORE THAN 31???2 IN. (90 MM) AT |
| EACH SIDE OF THE DOOR |
| OPENINGS AT A HEIGHT OF NOT MORE THAN 38 IN. (965 MM) |
| SHALL NOT BE |
| CONSIDERED REDUCTIONS IN EGRESS CAPACITY WIDTH. |
| (6) PROJECTIONS EXCEEDING 6 FT 8 IN. (2030 MM) ABOVE |
| THE FLOOR SHALL |
| NOT BE CONSIDERED REDUCTIONS IN EGRESS CAPACITY WIDTH. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE |
| SPECIFIC DETAILS. |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |