Plan Review Notes
Plan Review Notes For Permit 23060804
Permit Number 23060804
Review Stop B
Sequence Number 1
Notes
Date Text
2023-07-18 16:41:18NEW 8 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A1-05B - DOORS OPENING INTO THE CORRIDOR -
 PLEASE SHOW THAT THE DOORS COMPLY WITH FBC 1005.7.1
 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 2) PLEASE SHOW THE STAIR RISER HEIGHTS TO COMPLY WITH
 FBC 1011.5.2 RISER HEIGHT AND TREAD DEPTH.
 STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM
 AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL
 BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT
 TREADS.
  
 3) DRAWING S0-02 - WIND DESIGN DATA SHOWN SHOWS WIND
 SPEED AT 169MPH - SHOULD BE 170MPH PER FBC WPB SECTION
 120
  
 4) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE GROUND
 FLOOR GARAGE TO THE INTERIOR OF THE BUILDING (CORRIDOR,
 LOBBY, RETAIL - ETC.) FBC FHA REQUIREMENT 1 - (FBC A
 206.2.1)
  
 5) PLEASE SHOW THE UNIT BATHROOM WALLS ON THE FLOOR
 PLANS THAT ARE TO HAVE GRAB BAR BACKING - FBC WPB
 REQUIREMENT 6
  
 6) 8TH FLOOR CLUB ROOM - PLEASE SHOW THE ACCESSIBLE
 SEATING, BAR COUNTER HEIGHT, KNEE AND TOE CLEARANCE -
 FBC WPB REQUIREMENT 2
  
 7) GROUND FLOOR RESTAURANT - PLEASE SHOW THE ACCESSIBLE
 SEATING (INCLUDING THE BAR AREA - COUNTER HEIGHT, KNEE
 AND TOE CLEARANCE ETC.) FBC A 226
  
 8) JOB COST PER ICC VALUATION TABLE ADDS UP TO A JOB
 COST OF $52,504,636.00 - PLEASE REVISE THE BUILDING
 PERMIT APPLICATION OR PROVIDE A COST BREAK DOWN TO
 SUPPORT THE JOB COST SHOWN ON THE PROVIDED BUILDING
 PERMIT APPLICATION.
  
 9) THRESHOLD BUILDING INSPECTION FORMS - PLEASE READ
 AND FILL OUT THE REQUIRED DOCUMENTS AND PROVIDE COPIES
 OF THE LICENSES PER THE "GUIDELINES AND POLICIES FOR
 PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND
 RESIDENT INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A
 COPY.
  
 10) FOR THE UNIT FLOORING ASSEMBLIES - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED: ( FLOORING TEST
 REPORTS CAN BE ADDED TO THE DEFERRED SUBMITTALS LIST)
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  