2023-07-18 16:41:18 | NEW 8 STORY R2 |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DRAWING A1-05B - DOORS OPENING INTO THE CORRIDOR - |
| PLEASE SHOW THAT THE DOORS COMPLY WITH FBC 1005.7.1 |
| DOORS. |
| DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| THAN ONE-HALF. |
| |
| 2) PLEASE SHOW THE STAIR RISER HEIGHTS TO COMPLY WITH |
| FBC 1011.5.2 RISER HEIGHT AND TREAD DEPTH. |
| STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM |
| AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL |
| BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT |
| TREADS. |
| |
| 3) DRAWING S0-02 - WIND DESIGN DATA SHOWN SHOWS WIND |
| SPEED AT 169MPH - SHOULD BE 170MPH PER FBC WPB SECTION |
| 120 |
| |
| 4) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE GROUND |
| FLOOR GARAGE TO THE INTERIOR OF THE BUILDING (CORRIDOR, |
| LOBBY, RETAIL - ETC.) FBC FHA REQUIREMENT 1 - (FBC A |
| 206.2.1) |
| |
| 5) PLEASE SHOW THE UNIT BATHROOM WALLS ON THE FLOOR |
| PLANS THAT ARE TO HAVE GRAB BAR BACKING - FBC WPB |
| REQUIREMENT 6 |
| |
| 6) 8TH FLOOR CLUB ROOM - PLEASE SHOW THE ACCESSIBLE |
| SEATING, BAR COUNTER HEIGHT, KNEE AND TOE CLEARANCE - |
| FBC WPB REQUIREMENT 2 |
| |
| 7) GROUND FLOOR RESTAURANT - PLEASE SHOW THE ACCESSIBLE |
| SEATING (INCLUDING THE BAR AREA - COUNTER HEIGHT, KNEE |
| AND TOE CLEARANCE ETC.) FBC A 226 |
| |
| 8) JOB COST PER ICC VALUATION TABLE ADDS UP TO A JOB |
| COST OF $52,504,636.00 - PLEASE REVISE THE BUILDING |
| PERMIT APPLICATION OR PROVIDE A COST BREAK DOWN TO |
| SUPPORT THE JOB COST SHOWN ON THE PROVIDED BUILDING |
| PERMIT APPLICATION. |
| |
| 9) THRESHOLD BUILDING INSPECTION FORMS - PLEASE READ |
| AND FILL OUT THE REQUIRED DOCUMENTS AND PROVIDE COPIES |
| OF THE LICENSES PER THE "GUIDELINES AND POLICIES FOR |
| PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND |
| RESIDENT INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A |
| COPY. |
| |
| 10) FOR THE UNIT FLOORING ASSEMBLIES - THE FOLLOWING |
| ACUSTICAL TEST REPORTS ARE REQUIRED: ( FLOORING TEST |
| REPORTS CAN BE ADDED TO THE DEFERRED SUBMITTALS LIST) |
| |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| CEILING DESCRIPTION) |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| DROP CEILING DESCRIPTION) |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| ATTACHED TO THE FLOORING) |
| |
| |