2023-06-20 14:09:52 | ELECTRICAL REVIEW FAILED |
| 1) COVER SHEET DETAILS PATIO ENCLOSURE AS HABITABLE AND |
| NON-HABITABLE. PLEASE EXPLAIN HOW THIS ROOM CAN BE |
| BOTH. FBC 107.2 |
| 2) ELECTRICAL RECEPTACLE SPACING DOES NOT APPEAR TO BE |
| COMPLIANT WITH NEC 210.52. PLEASE CORRECT AS APPLICABLE |
| 3) PLEASE PROVIDE REFERENCE TO KEYED NOTES ON SHEET S2. |
| PLAN DOES NOT DETAIL IF THERE ARE OPERABLE DOORS |
| LEADING TO THE EXTERIOR FBC 107.2 |
| 4) PLEASE DETAIL COMPLIANCE WITH NEC 210.70(2)(2). FOR |
| CONTROLLED LIGHTING OUTLET ON THE EXTERIOR OF DOORS TO |
| PROVIDE ILLUMINATION |
| 5) PLANS DO NOT DETAIL THE REQUIRED DIGITAL SIGNATURE |
| OF TROY BISHOP PE. PLEASE CORRECT AS OUTLINE BELOW. |
| FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF |
| RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| DIGITALLY SEALED AND SIGNED. |
| |
| PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS |
| FOLLOWING PROJECTDOX INSTRUCTIONS |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |