2023-06-20 14:09:52ELECTRICAL REVIEW FAILED
 1) COVER SHEET DETAILS PATIO ENCLOSURE AS HABITABLE AND
 NON-HABITABLE. PLEASE EXPLAIN HOW THIS ROOM CAN BE
 BOTH. FBC 107.2
 2) ELECTRICAL RECEPTACLE SPACING DOES NOT APPEAR TO BE
 COMPLIANT WITH NEC 210.52. PLEASE CORRECT AS APPLICABLE
 3) PLEASE PROVIDE REFERENCE TO KEYED NOTES ON SHEET S2.
 PLAN DOES NOT DETAIL IF THERE ARE OPERABLE DOORS
 LEADING TO THE EXTERIOR FBC 107.2
 4) PLEASE DETAIL COMPLIANCE WITH NEC 210.70(2)(2). FOR
 CONTROLLED LIGHTING OUTLET ON THE EXTERIOR OF DOORS TO
 PROVIDE ILLUMINATION
 5) PLANS DO NOT DETAIL THE REQUIRED DIGITAL SIGNATURE
 OF TROY BISHOP PE. PLEASE CORRECT AS OUTLINE BELOW.
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  