Plan Review Notes
Plan Review Notes For Permit 23060646
Permit Number 23060646
Review Stop B
Sequence Number 1
Notes
Date Text
2023-07-05 10:23:19FBC 1072.1
  
 1. PROVIDE CLEAR SURVEY OR SITE PLAN WITH GATE AND
 FENCE TO SCALE DIMENSIONS, SET BACK AND IF ANY EASEMNT,
 CLEARANCE WILL BE REQUIRED.
 2 PROVIDE POSTS FOUNDATION IN SECTION AND CLEARLY
 INDICATE HEIGHT AT EACH POSTS. SHOW DIMENSIONS IN
 BETWEEN PICKETS, PROVIDE LATCH AND LOCK DETAILS.
  
 ???R4501.17.1.8 ACCESS GATES, WHEN PROVIDED, SHALL BE
 SELF-CLOSING AND SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTIONS R4501.17.1.1 THROUGH R4501.17.1.7 AND
 SHALL BE EQUIPPED WITH A SELF-LATCHING LOCKING DEVICE
 LOCATED ON THE POOL SIDE OF THE GATE. WHERE THE
 DEVICE RELEASE IS LOCATED NO LESS THAN 54 INCHES
 (1372 MM) FROM THE BOTTOM OF THE GATE, THE DEVICE
 RELEASE MECHANISM MAY BE LOCATED ON EITHER SIDE OF
 THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY A
 YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR
 GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO
 THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE
 POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM
  
  