Plan Review Notes
Plan Review Notes For Permit 23060584
Permit Number 23060584
Review Stop B
Sequence Number 1
Notes
Date Text
2023-06-26 08:44:53PERMIT- 23060584
 6.26.2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. CLARIFY IF THE EXISTING TUB DRAIN WILL BE RE-USED OR
 IF A NEW DRAIN WILL BE INSTALLED IN THE CENTER OF THE
 SHOWER. PLEASE NOTE THE FOLLOWING FOR NEW DRAIN
 INSTALLATIONS:
 RELOCATING THE SHOWER DRAIN OUTLET MAY REQUIRE THE
 FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING
 STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A
 NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET-
 SECTION 107.2.1 WPB.
 NEW DRAINPIPE PENETRATIONS OF THE EXISTING SLAB WILL
 REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE AROUND
 THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 2. [FBC 1207.3] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES
 BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A
 DWELLING
 UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS
 RATING OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 WHEN TESTED
 IN ACCORDANCE WITH ASTM E492.
  
 3. [FBC 603.1] ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 PROVIDE PROPOSED NEW FLOORING NOA OF FBC PRODUCT
 APPROVAL AND SPECS SAME FOR UNDERLAYMENT. FLAME SPREAD,
 ACCOUSTIC PROPERTY AND SOUND TEST DOCUMENTATION
 REQUIRED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved